| Parameter | Value |
|---|---|
| GTIN | 4017918182847 |
| Orderkey | 2839185 |
| (General) | PT -BE/ FM 2839282 |
| Catalog page | Page 114 (C-4-2017) |
| Packing unit | 10 pc |
| Note (General) | Technical data is valid in association with the following specified base elements: |
| Country of origin | DE (Germany) |
| (Connection data) | EN 61643-21 2001 + A1:2009 + A2:2013 |
| Custom tariff number | 85363010 |
| Altitude (Dimensions) | ≤ 2000 m (amsl (above mean sea level)) |
| Type (Ambient conditions) | Male |
| (Additional descriptions) | D1 - 500 A |
| Color (Ambient conditions) | jet black RAL 9005 |
| Depth (Key Commercial Data) | 51.7 mm |
| Width (Key Commercial Data) | 17.5 mm |
| Height (Key Commercial Data) | 44.8 mm |
| Degree of protection (Dimensions) | IP20 |
| Screw thread (Protective circuit) | M3 |
| Mounting type (Ambient conditions) | on base element |
| Weight per Piece (excluding packing) | 23.620 g |
| Housing material (Ambient conditions) | PA 6.6 |
| Stripping length (Protective circuit) | 8 mm |
| Connection method (Protective circuit) | Screw connection (in connection with the base element) |
| Horizontal pitch (Key Commercial Data) | 1 Div. |
| Tightening torque (Protective circuit) | 0.5 Nm |
| Rated current (Additional descriptions) | 26 A AC (30 °C) |
| Direction of action (Ambient conditions) | Line-Line & Line-Earth Ground |
| Standards/specifications (Connection data) | IEC 61643 2000 + corrigendum 2001 + A1:2008, modified + A2:2012 |
| Complete module depth (Key Commercial Data) | 65.5 mm |
| Complete module width (Key Commercial Data) | 17.7 mm |
| Ambient temperature (operation) (Dimensions) | -40 °C ... 85 °C |
| Complete module height (Key Commercial Data) | 90 mm |
| Nominal voltage UN (Additional descriptions) | 120 V AC (50/60 Hz) |
| Residual current IPE (Additional descriptions) | ≤ 3 mA AC |
| Capacity (line-earth) (Additional descriptions) | typ. 2.5 nF |
| Conductor cross section AWG (Protective circuit) | 24 ... 12 |
| IEC test classification (Additional descriptions) | C1 |
| Conductor cross section solid (Protective circuit) | 0.2 mm² ... 4 mm² |
| Ambient temperature (storage/transport) (Dimensions) | -40 °C ... 85 °C |
| Max. required back-up fuse (Additional descriptions) | 25 A AC (gL/gG) |
| Conductor cross section flexible (Protective circuit) | 0.2 mm² ... 2.5 mm² |
| Input attenuation aE, asym. (Additional descriptions) | typ. 0.3 dB (≤ 300 kHz / 150 Ω) |
| Response time tA(line-earth) (Additional descriptions) | ≤ 25 ns |
| Maximum continuous voltage UC (Additional descriptions) | 150 V DC |
| Surge protection fault message (Additional descriptions) | none |
| Impulse durability (line-earth) (Additional descriptions) | C1 - 1,4 kV / 0,7 kA |
| Flammability rating according to UL 94 (Ambient conditions) | V-0 |
| Operating effective current ICat UC (Additional descriptions) | ≤ 1.5 mA AC |
| Voltage protection level Up(line-earth) (Additional descriptions) | ≤ 450 V (C1 - 1.4 kV / 0.7 kA) |
| Pulse discharge current Iimp(10/350) µs (Additional descriptions) | 500 A |
| Total discharge current Itotal(8/20) µs (Additional descriptions) | 5 kA |
| Nominal discharge current In(8/20) µs (line-earth) (Additional descriptions) | 2.5 kA |
| Output voltage limitation at 1 kV/µs (line-earth) spike (Additional descriptions) | ≤ 380 V |
| Arrester can be tested with CHECKMASTER from software version: (Ambient conditions) | From SW rev. 1.00 |
| Output voltage limitation at 1 kV/µs (line-earth) static (Additional descriptions) | ≤ 380 V |
| Cut-off frequency fg (3 dB), asym. (GND) in 150 Ohm system (Additional descriptions) | typ. 1 MHz |
Technical specifications and performance data