| Parameter | Value |
|---|---|
| GTIN | 4046356460989 |
| Orderkey | 2805460 |
| (General) | D1 - 500 A |
| Catalog page | Page 114 (C-4-2017) |
| Packing unit | 10 pc |
| Country of origin | DE (Germany) |
| Custom tariff number | 85363010 |
| Rated current (General) | 6 A |
| Type (Ambient conditions) | DIN rail module, two-section, divisible |
| Color (Ambient conditions) | black |
| Response time tA (General) | ≤ 100 ns |
| Depth (Key Commercial Data) | 51.7 mm |
| Energy absorption (General) | 150 J |
| Width (Key Commercial Data) | 17.5 mm |
| Height (Key Commercial Data) | 44.8 mm |
| Nominal voltage UN (General) | 230 V AC |
| Capacity (line-line) (General) | typ. 4.5 pF |
| Residual current IPE (General) | ≤ 2 µA (at UN) |
| Resistance in series (General) | 0 Ω |
| Capacity (line-earth) (General) | typ. 9 pF |
| Degree of protection (Dimensions) | IP20 |
| IEC test classification (General) | C1 |
| Screw thread (Protective circuit) | M3 |
| Mounting type (Ambient conditions) | DIN rail: 35 mm |
| Connection method (Connection data) | Screw connection |
| Max. required back-up fuse (General) | 6 A (gL / gG) |
| Weight per Piece (excluding packing) | 71.780 g |
| Housing material (Ambient conditions) | PA 6.6 |
| Stripping length (Protective circuit) | 8 mm |
| Connection method (Protective circuit) | Screw connection |
| Horizontal pitch (Key Commercial Data) | 1 Div. |
| Tightening torque (Protective circuit) | 0.8 Nm |
| Maximum continuous voltage UC (General) | 250 V AC |
| Direction of action (Ambient conditions) | Line-Line & Line-Earth Ground |
| Number of positions (Ambient conditions) | 2 |
| Surge protection fault message (General) | optical |
| Tightening torque, min (Connection data) | 0.8 Nm |
| Connection method IN (Protective circuit) | Screw terminal blocks |
| Impulse durability (line-earth) (General) | C2 - 4 kV/2 kA |
| Connection method OUT (Protective circuit) | Screw terminal blocks |
| Complete module depth (Key Commercial Data) | 65.5 mm |
| Complete module width (Key Commercial Data) | 17.7 mm |
| Residual voltage at In(line-line) (General) | ≤ 2 kV |
| Ambient temperature (operation) (Dimensions) | -40 °C ... 80 °C |
| Complete module height (Key Commercial Data) | 90 mm |
| Residual voltage at In(line-earth) (General) | ≤ 1 kV |
| Operating effective current ICat UC (General) | ≤ 2 µA |
| Max. discharge current Imax(8/20) µs (General) | 8 kA |
| Conductor cross section AWG (Protective circuit) | 24 ... 12 |
| Nominal discharge current In(8/20) µs (General) | 3 kA |
| Voltage protection level Up(line-line) (General) | ≤ 2.5 kV (C2 - 4 kV / 2 kA) |
| Standards/regulations (Remote indication contact) | DIN EN 61643-21 |
| Voltage protection level Up(line-earth) (General) | ≤ 1.1 kV (C1 - 500 A) |
| Conductor cross section solid (Protective circuit) | 0.2 mm² ... 4 mm² |
| Pulse discharge current Iimp(10/350) µs (General) | 500 A |
| Total discharge current Itotal(8/20) µs (General) | 8 kA |
| Standards/specifications (Remote indication contact) | DIN EN 61643-21 2002 |
| Total discharge current Itotal(10/350) µs (General) | 1 kA |
| Conductor cross section flexible (Protective circuit) | 0.2 mm² ... 2.5 mm² |
| Switching function (Connection, equipotential bonding) | N/C contact |
| Flammability rating according to UL 94 (Ambient conditions) | V-0 |
| Nominal discharge current In(8/20) µs (line-earth) (General) | 3 kA |
| Residual voltage with Ian (10/1000) µs (line-line) (General) | ≤ 1.4 kV |
| Nominal pulse current Ian (10/1000) µs (line-earth) (General) | 100 A |
| Residual voltage with Ian (10/1000) µs (line-earth) (General) | ≤ 700 V |
| Max. operating current Imax (Connection, equipotential bonding) | 1 A |
| Output voltage limitation at 1 kV/µs (line-earth) static (General) | ≤ 1.4 kV |
| Max. discharge current Imax(8/20) µs maximum (line-earth) (General) | 8 kA |
| Maximum operating voltage Umax.AC (Connection, equipotential bonding) | 250 V AC |