| Parameter | Value |
|---|---|
| GTIN | 4017918974558 |
| Note | Made to Order (non-returnable) |
| Orderkey | 2856799 |
| (General) | C3 - 25 A |
| Catalog page | Page 114 (C-4-2017) |
| Packing unit | 10 pc |
| Country of origin | DE (Germany) |
| Capacity (General) | typ. 3 pF |
| Custom tariff number | 85363010 |
| (Ambient conditions) | DIN VDE 0110-1 |
| Rated current (General) | 6 A (with PT BE/FM) |
| Type (Ambient conditions) | Male |
| Color (Ambient conditions) | black |
| Response time tA (General) | ≤ 100 ns |
| Depth (Key Commercial Data) | 51.7 mm |
| Energy absorption (General) | 85 J |
| Width (Key Commercial Data) | 17.5 mm |
| (Remote indication contact) | IEC 61643-21 |
| Height (Key Commercial Data) | 44.8 mm |
| Nominal voltage UN (General) | 120 V AC |
| Residual current IPE (General) | ≤ 4 µA |
| Resistance in series (General) | 0 Ω |
| Degree of protection (Dimensions) | IP20 |
| IEC test classification (General) | C1 |
| Mounting type (Ambient conditions) | on base element |
| Max. required back-up fuse (General) | 6 A (with PT BE/FM) |
| Switching function (Connection data) | N/C contact |
| Weight per Piece (excluding packing) | 25.600 g |
| Housing material (Ambient conditions) | PA 6.6 |
| Voltage protection level Up (General) | ≤ 1 kV (C2 - 2 kA) |
| Connection method (Protective circuit) | Screw connection (in connection with the base element) |
| Horizontal pitch (Key Commercial Data) | 1 Div. |
| Maximum continuous voltage UC (General) | 175 V AC |
| Degree of pollution (Ambient conditions) | 2 |
| Direction of action (Ambient conditions) | Line-Line & Line-Earth Ground |
| Number of positions (Ambient conditions) | 2 |
| Surge protection fault message (General) | none |
| Impulse durability (line-earth) (General) | C1 - 1 kV/500 A |
| Overvoltage category (Ambient conditions) | III |
| Complete module depth (Key Commercial Data) | 65.5 mm |
| Complete module width (Key Commercial Data) | 17.7 mm |
| Ambient temperature (operation) (Dimensions) | -40 °C ... 80 °C |
| Complete module height (Key Commercial Data) | 90 mm |
| Residual voltage at In(line-earth) (General) | ≤ 600 V |
| Max. operating current Imax (Connection data) | 3 A |
| Operating effective current ICat UC (General) | ≤ 2 µA |
| Max. discharge current Imax(8/20) µs (General) | 8 kA |
| Nominal discharge current In(8/20) µs (General) | 3 kA |
| Standards/regulations (Remote indication contact) | EN 61643-21 |
| Voltage protection level Up(line-earth) (General) | ≤ 900 V (C1 - 500 A) |
| Pulse discharge current Iimp(10/350) µs (General) | 300 A |
| Maximum operating voltage Umax.AC (Connection data) | 120 V AC |
| Standards/specifications (Remote indication contact) | EN 61643-21 2002 |
| Total discharge current Itotal(10/350) µs (General) | 8 kA |
| Flammability rating according to UL 94 (Ambient conditions) | V-0 |
| Nominal pulse current Ian (10/1000) µs (line-earth) (General) | 40 A |
| Residual voltage with Ian (10/1000) µs (line-earth) (General) | ≤ 360 V |
| Output voltage limitation at 1 kV/µs (line-earth) static (General) | ≤ 800 V |
| Standards for cearances and creepage distances (Ambient conditions) | IEC 60664-1 |
| Arrester can be tested with CHECKMASTER from software version: (Ambient conditions) | SW Version 2.13 or later |
Technical specifications and performance data