| Parameter | Value |
|---|---|
| GTIN | 4046356154079 |
| Orderkey | 2920120 |
| (General) | C3 - 25 A |
| Catalog page | Page 91 (TT-2011) |
| Depth (Note) | 51.7 mm |
| Packing unit | 10 pc |
| Width (Note) | 17.5 mm |
| Height (Note) | 44.8 mm |
| Country of origin | DE (Germany) |
| (Connection data) | 1 A (60 V DC) |
| Custom tariff number | 85363010 |
| (Ambient conditions) | IEC 60664-1 |
| Horizontal pitch (Note) | 1 Div. |
| Rated current (General) | 300 mA (45°C) |
| Type (Ambient conditions) | Male |
| Color (Ambient conditions) | black |
| (Remote indication contact) | DIN EN 61643-21 |
| (Standards and Regulations) | No hazardous substances above threshold values |
| Complete module depth (Note) | 65.5 mm |
| Complete module width (Note) | 17.7 mm |
| Nominal voltage UN (General) | 24 V DC |
| Complete module height (Note) | 90 mm |
| Residual current IPE (General) | ≤ 1 µA (with PT 2X1+F-BE) |
| Resistance in series (General) | 4.7 Ω (7-8/11-12) |
| VDE requirement class (General) | C1 |
| Degree of protection (Dimensions) | IP20 |
| IEC test classification (General) | C1 |
| Screw thread (Protective circuit) | M3 |
| Mounting type (Ambient conditions) | on base element |
| Max. required back-up fuse (General) | 315 mA (T) |
| Switching function (Connection data) | N/C contact |
| Weight per Piece (excluding packing) | 27.180 g |
| Housing material (Ambient conditions) | PA 6.6 |
| Input attenuation aE, asym. (General) | typ. 0.5 dB (≤ 1 MHz / 50 Ω) |
| Stripping length (Protective circuit) | 8 mm |
| China RoHS (Standards and Regulations) | Environmentally friendly use period: unlimited = EFUP-e |
| Connection method (Protective circuit) | Screw connection (in connection with the base element) |
| Response time tA(line-earth) (General) | ≤ 1 ns |
| Standby power consumption PC (General) | ≤ 1.73 VA |
| Tightening torque (Protective circuit) | 0.8 Nm |
| Maximum continuous voltage UC (General) | 28 V DC |
| Direction of action (Ambient conditions) | Line-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-Earth Ground |
| Surge protection fault message (General) | Optical, remote indicator contact |
| Impulse durability (line-earth) (General) | C2 - 10 kV/5 kA |
| Ambient temperature (operation) (Dimensions) | -40 °C ... 85 °C |
| Residual voltage at In(line-earth) (General) | ≤ 40 V |
| Max. operating current Imax (Connection data) | 0.2 A (250 V AC) |
| Operating effective current ICat UC (General) | ≤ 5 µA |
| Utilization restriction (Key Commercial Data) | EMC: class A product, see manufacturer's declaration in the download area |
| Conductor cross section AWG (Protective circuit) | 24 ... 12 |
| Standards/regulations (Remote indication contact) | IEC 61643-21 |
| Voltage protection level Up(line-earth) (General) | ≤ 40 V (C1 - 500 V / 250 A) |
| Conductor cross section solid (Protective circuit) | 0.2 mm² ... 4 mm² |
| Pulse discharge current Iimp(10/350) µs (General) | 2.5 kA (per path) |
| Total discharge current Itotal(8/20) µs (General) | 20 kA |
| Maximum operating voltage Umax.AC (Connection data) | 250 V AC |
| Standards/specifications (Remote indication contact) | IEC 61643-21 2002 |
| Conductor cross section flexible (Protective circuit) | 0.2 mm² ... 2.5 mm² |
| Voltage protection level Up(line-signalground) (General) | ≤ 40 V (C1 - 500 V / 250 A) |
| Flammability rating according to UL 94 (Ambient conditions) | V-0 |
| Alternating current carrying capacity (line-earth) (General) | 5 A - 1 s |
| Nominal discharge current In(8/20) µs (line-earth) (General) | 10 kA |
| Nominal pulse current Ian (10/1000) µs (line-earth) (General) | 33 A (25 °C) |
| Residual voltage with Ian (10/1000) µs (line-earth) (General) | ≤ 50 V |
| Output voltage limitation at 1 kV/µs (line-earth) spike (General) | ≤ 50 V |
| Cut-off frequency fg (3 dB), asym. (GND) in 50 Ohm system (General) | typ. 6 MHz |
| Output voltage limitation at 1 kV/µs (line-earth) static (General) | ≤ 40 V |
| Standards for cearances and creepage distances (Ambient conditions) | VDE 0110-1 |
| Cut-off frequency fg (3 dB), asym. (GND) in 150 Ohm system (General) | typ. 2.5 MHz |
| Max. discharge current Imax(8/20) µs maximum (line-earth) (General) | 10 kA |
| Output voltage limitation at 1 kV/µs (line-signalground) spike (General) | ≤ 50 V |
| Output voltage limitation at 1 kV/µs (line-signalground) static (General) | ≤ 40 V |