Service time: Monday to Friday 9:00-18:00
PT 2X1-24AC-ST - PT 2X1-24AC-ST 2856100 PHOENIX CONTACT Surge protection plug
In Stock Hot Product

PT 2X1-24AC-ST

PT 2X1-24AC-ST 2856100 PHOENIX CONTACT Surge protection plug

$0.00USD
4686 in stock
Key Specifications
GTIN:4017918599140
Orderkey:2856100
(General):PT 2X1-BE 2856139
Catalog page:Page 113 (C-4-2017)
Supplier Information
Products: 0
Usually ships within 2-3 business days
Quality Guaranteed
Fast Shipping
Technical Support

Technical Specifications

ParameterValue
GTIN4017918599140
Orderkey2856100
(General)PT 2X1-BE 2856139
Catalog pagePage 113 (C-4-2017)
Packing unit10 pc
Note (General)Technical data is valid in association with the following specified base elements:
Country of originDE (Germany)
(Connection data)EN 61643-21 2001 + A1:2009 + A2:2013
Custom tariff number85363010
Altitude (Dimensions)≤ 2000 m (amsl (above mean sea level))
Type (Ambient conditions)Male
(Additional descriptions)D1 - 2.5 kA
Color (Ambient conditions)jet black RAL 9005
Depth (Key Commercial Data)51.7 mm
Width (Key Commercial Data)17.5 mm
Height (Key Commercial Data)44.8 mm
Degree of protection (Dimensions)IP20
Screw thread (Protective circuit)M3
Mounting type (Ambient conditions)on base element
Weight per Piece (excluding packing)19.850 g
Housing material (Ambient conditions)PA 6.6
Stripping length (Protective circuit)8 mm
Connection method (Protective circuit)Screw connection (in connection with the base element)
Horizontal pitch (Key Commercial Data)1 Div.
Tightening torque (Protective circuit)0.5 Nm
Rated current (Additional descriptions)300 mA (45°C)
Direction of action (Ambient conditions)Line-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-Earth Ground
Standards/specifications (Connection data)IEC 61643-21 2000 + corrigendum 2001 + A1:2008, modified + A2:2012
Complete module depth (Key Commercial Data)65.5 mm
Complete module width (Key Commercial Data)17.7 mm
Ambient temperature (operation) (Dimensions)-40 °C ... 85 °C
Complete module height (Key Commercial Data)90 mm
Nominal voltage UN (Additional descriptions)24 V AC
Residual current IPE (Additional descriptions)≤ 1 µA (with PT 2X1+F-BE)
Resistance in series (Additional descriptions)4.7 Ω ±10 %
Capacity (line-earth) (Additional descriptions)typ. 0.6 nF (with PT 2x1-BE)
Conductor cross section AWG (Protective circuit)24 ... 12
IEC test classification (Additional descriptions)C1
Conductor cross section solid (Protective circuit)0.2 mm² ... 4 mm²
Ambient temperature (storage/transport) (Dimensions)-40 °C ... 85 °C
Max. required back-up fuse (Additional descriptions)315 mA (T)
Conductor cross section flexible (Protective circuit)0.2 mm² ... 2.5 mm²
Input attenuation aE, asym. (Additional descriptions)typ. 0.5 dB (≤ 1.5 MHz / 50 Ω)
Response time tA(line-earth) (Additional descriptions)≤ 1 ns (with PT 2x1-BE)
Maximum continuous voltage UC (Additional descriptions)40 V DC
Surge protection fault message (Additional descriptions)none
Impulse durability (line-earth) (Additional descriptions)C2 - 10 kV/5 kA
Flammability rating according to UL 94 (Ambient conditions)V-0
Residual voltage at In(line-earth) (Additional descriptions)≤ 55 V
Operating effective current ICat UC (Additional descriptions)≤ 5 µA
Response time tA (line-signalground) (Additional descriptions)≤ 1 ns (with PT 2X1+F-BE)
Voltage protection level Up(line-earth) (Additional descriptions)≤ 100 V (C2 - 10 kV/5 kA with PT 2X1-BE)
Pulse discharge current Iimp(10/350) µs (Additional descriptions)2.5 kA
Total discharge current Itotal(8/20) µs (Additional descriptions)20 kA
Voltage protection level Upstatic (line-earth) (Additional descriptions)≤ 30 V (C2 - 10 kV/5 kA with PT 2X1-BE)
Nominal discharge current In(8/20) µs (line-earth) (Additional descriptions)10 kA
Nominal pulse current Ian (10/1000) µs (line-earth) (Additional descriptions)23 A
Residual voltage with Ian (10/1000) µs (line-earth) (Additional descriptions)≤ 65 V
Cut-off frequency fg (3 dB), asym. (PE) in 50 Ohm system (Additional descriptions)typ. 8 MHz
Output voltage limitation at 1 kV/µs (line-earth) spike (Additional descriptions)≤ 60 V (with PT 2x1-BE)
Arrester can be tested with CHECKMASTER from software version: (Ambient conditions)From SW rev. 1.00
Cut-off frequency fg (3 dB), asym. (PE) in 150 Ohm system (Additional descriptions)typ. 300 kHz
Cut-off frequency fg (3 dB), asym. (PE) in 600 Ohm system (Additional descriptions)typ. 800 kHz
Output voltage limitation at 1 kV/µs (line-earth) static (Additional descriptions)≤ 55 V (with PT 2x1-BE)
Max. discharge current Imax(8/20) µs maximum (line-earth) (Additional descriptions)10 kA

Product Description

Plug-in surge protection for base element, coarse and fine protection for two signal conductors with common reference potential, coarse protection against longitudinal voltage to earth. Workmanship: 2
Key Features
  • Industrial grade quality
  • RoHS compliant
  • CE certified
  • 1-year warranty

Product Documents

Datasheet

Technical specifications and performance data

User Manual

Installation and operation guide

Top