Key Specifications
:PT 1X2+F-BE 2856126
Note:Technical data is valid in association with the following specified base elements:
Type:Male
Color:black (RAL 9005)
Supplier Information
Products: 0
Usually ships within 2-3 business days
Quality Guaranteed
Fast Shipping
Technical Support

Technical Specifications

ParameterValue
PT 1X2+F-BE 2856126
NoteTechnical data is valid in association with the following specified base elements:
TypeMale
Colorblack (RAL 9005)
Depth52 mm
Width17.7 mm
Height45 mm
Altitude≤ 2000 m (amsl)
Product typeSurge protection for MCR technology
Screw threadM3
Mounting typeon base element
Rated current450 mA (45 °C)
Product familyPLUGTRAB PT
Open side panelNo
Article revision18
Horizontal pitch1 Div.
Housing materialPA 6.6
Pollution degree2
Connection methodScrew connection (in connection with the base element)
Tightening torque0.5 Nm
Nominal voltage UN24 V AC
Dimensional drawing
Direction of actionLine-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-Earth Ground
Number of positions2
Resistance per path2.2 Ω ±10 %
Capacity (Core-Core)typ. 1.1 nF
Degree of protectionIP20
Overvoltage categoryIII
Residual current IPE≤ 1 µA (with PT 1X2+F-BE)
Capacity (Core-Earth)typ. 4 pF (with PT 1X2-BE)
Complete module depth65.5 mm
Complete module width17.7 mm
Wire pairs per module1
Complete module height90 mm
IEC test classificationC1
Standards/specificationsIEC 61643-21
Input attenuation aE, sym.typ. 0.5 dB (≤ 1.5 MHz / 50 Ω)
Max. required back-up fuse500 mA (T)
Conductor cross section AWG24 ... 12
Response time tA(line-line)≤ 1 ns
Response time tA(line-earth)≤ 100 ns
Conductor cross section rigid0.2 mm² ... 4 mm²
Maximum continuous voltage UC40 V DC
Impulse durability (line-line)C2 - 10 kV / 5 kA
Surge protection fault messagenone
Ambient temperature (operation)-40 °C ... 85 °C
Impulse durability (line-earth)C1 - 1 kV / 500 A
Conductor cross section flexible0.2 mm² ... 2.5 mm²
Operating effective current ICat UC≤ 5 A
Flammability rating according to UL 94V-0
Voltage protection level Up(line-line)≤ 80 V (C2 - 10 kV / 5 kA)
Ambient temperature (storage/transport)-40 °C ... 85 °C
Voltage protection level Up(line-earth)≤ 450 V (C1 - 1 kV / 500 A with PT 1X2-BE)
Pulse discharge current Iimp(10/350) µs2.5 kA
Total discharge current Itotal(8/20) µs20 kA
Residual voltage at In(conductor-conductor)≤ 55 V
Voltage protection level Upstatic (line-line)≤ 50 V (C2 - 10 kV / 5 kA)
Voltage protection level Upstatic (line-earth)≤ 50 V (C2 - 10 kV / 5 kA with PT 1X2-BE)
Nominal discharge current In(8/20) µs (line-line)10 kA
Cut-off frequency fg (3 dB), sym. in 50 Ω systemtyp. 8 MHz
Nominal pulse current Ian (10/1000) µs (line-line)23 A
Residual voltage with Ian (10/1000) µs (line-line)≤ 65 V
Cut-off frequency fg (3 dB), sym. in 150 Ω systemtyp. 3 MHz
Cut-off frequency fg (3 dB), sym. in 600 Ω systemtyp. 800 kHz
Nominal discharge current In(8/20) µs (line-ground)10 kA
Output voltage limitation at 1 kV/µs (line-line) spike≤ 55 V
Output voltage limitation at 1 kV/µs (line-earth) spike≤ 450 V (with PT 1X2-BE)
Output voltage limitation at 1 kV/µs (line-line) static≤ 55 V
Max. discharge current Imax(8/20) µs maximum (line-line)10 kA
Output voltage limitation at 1 kV/µs (line-earth) static≤ 25 V (with PT 1X2-BE)
Max. discharge current Imax(8/20) µs maximum (line-earth)10 kA
Arrester can be tested with CHECKMASTER from software version:From SW rev. 1.00

Product Description

PT plug-in protection with circ. Protec. P/ un Circ. 2 cond. floating. Suitable for HART.
Key Features
  • Industrial grade quality
  • RoHS compliant
  • CE certified
  • 1-year warranty