| Parameter | Value |
|---|---|
| GTIN | 4055626309026 |
| Note | Made to Order (non-returnable) |
| Orderkey | 2908551 |
| (General) | 440 V AC (120 min / withstand mode) |
| Catalog page | Page 70 (C-4-2017) |
| Packing unit | 10 pc |
| Country of origin | CN (China) |
| (UL specifications) | EN 61643-11 2012 |
| Custom tariff number | 85363010 |
| (Ambient conditions) | N-PE |
| (Protective circuit) | L-G |
| Altitude (Dimensions) | ≤ 5000 m (amsl (above mean sea level)) |
| Minimum order quantity | 10 pc |
| Type (Ambient conditions) | PCB onboard surge protector |
| Color (Ambient conditions) | light grey RAL 7035 |
| Depth (Key Commercial Data) | 25.3 mm |
| Width (Key Commercial Data) | 24 mm |
| EN type (Ambient conditions) | T2 |
| Height (Key Commercial Data) | 15.7 mm |
| Nominal voltage UN (General) | 230 V AC (TN) |
| SPD Type (Protective circuit) | 4CA |
| Nominal frequency fN (General) | 50 Hz (60 Hz) |
| Response time tA(L-N) (General) | ≤ 25 ns |
| Response time tA(L-PE) (General) | ≤ 100 ns |
| Response time tA(N-PE) (General) | ≤ 100 ns |
| Degree of protection (Dimensions) | IP20 |
| Nom. voltage (Protective circuit) | 230 V AC |
| TOV behavior at UT(L-N) (General) | 336 V AC (5 s / withstand mode) |
| Mounting type (Ambient conditions) | PCB mounting |
| TOV behavior at UT(N-PE) (General) | 1200 V AC (200 ms / withstand mode) |
| Weight per Piece (excluding packing) | 22.300 g |
| Housing material (Ambient conditions) | PA 6.6 |
| Voltage protection level Up (General) | ≤ 1.5 kV |
| Nominal frequency (Protective circuit) | 50/60 Hz |
| Maximum continuous voltage UC (General) | 350 V AC |
| Mode of protection (Ambient conditions) | L-N |
| Mode of protection (Protective circuit) | L-N |
| Degree of pollution (Ambient conditions) | 2 |
| Standards/regulations (UL specifications) | IEC 61643-11 2011 |
| Ambient temperature (operation) (Dimensions) | -40 °C ... 85 °C |
| IEC power supply system (Ambient conditions) | TN-S |
| IEC test classification (Ambient conditions) | II |
| Short-circuit current rating ISCCR (General) | 1 kA |
| Max. backup fuse with branch wiring (General) | 16 A AC (MCB B/general purpose) |
| Permissible humidity (operation) (Dimensions) | 5 % ... 95 % |
| Power distribution system (Protective circuit) | Single phase |
| Nominal discharge current In(8/20) µs (General) | 5 kA |
| Surge protection fault message (Ambient conditions) | optical |
| Ambient temperature (storage/transport) (Dimensions) | -40 °C ... 105 °C |
| Nominal discharge current In(L-N) (Protective circuit) | 5 kA |
| Measured limiting voltage MLV (L-G) (Protective circuit) | 1400 V |
| Measured limiting voltage MLV (L-N) (Protective circuit) | 1400 V |
| Measured limiting voltage MLV (N-G) (Protective circuit) | 1400 V |
| Flammability rating according to UL 94 (Ambient conditions) | V-0 |
| Maximum continuous operating voltage MCOV (Protective circuit) | 350 V AC |
| Maximum continuous operating voltage MCOV (L-G) (Protective circuit) | 350 V AC |
| Maximum continuous operating voltage MCOV (L-N) (Protective circuit) | 350 V AC |
| Maximum continuous operating voltage MCOV (N-G) (Protective circuit) | 350 V AC |
Technical specifications and performance data
Installation and operation guide