| Parameter | Value |
|---|---|
| GTIN | 4055626287607 |
| Note | Made to Order (non-returnable) |
| Orderkey | 2905977 |
| (General) | 440 V AC (120 min / withstand mode) |
| Catalog page | Page 70 (C-4-2017) |
| Packing unit | 20 pc |
| Country of origin | CN (China) |
| Custom tariff number | 85363010 |
| (Ambient conditions) | N-PE |
| (Protective circuit) | 1 A DC |
| Altitude (Dimensions) | ≤ 2000 m (amsl (above mean sea level)) |
| Minimum order quantity | 20 pc |
| Type (Ambient conditions) | PCB onboard surge protector |
| Color (Ambient conditions) | light grey RAL 7035 |
| Depth (Key Commercial Data) | 22.4 mm |
| Width (Key Commercial Data) | 38.4 mm |
| EN type (Ambient conditions) | T2 |
| Height (Key Commercial Data) | 41 mm |
| Nominal voltage UN (General) | 230 V AC (TN) |
| (Indicator/remote signaling) | EN 61643-11 2012 |
| Nominal frequency fN (General) | 50 Hz (60 Hz) |
| Residual current IPE (General) | ≤ 50 µA |
| Shock (operation) (Dimensions) | 25g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z) |
| Response time tA(L-N) (General) | ≤ 25 ns |
| Response time tA(L-PE) (General) | ≤ 100 ns |
| Response time tA(N-PE) (General) | ≤ 100 ns |
| TOV behavior at UT(L-N) (General) | 336 V AC (5 s / withstand mode) |
| Mounting type (Ambient conditions) | PCB mounting |
| TOV behavior at UT(N-PE) (General) | 1200 V AC (200 ms / safe failure mode) |
| Vibration (operation) (Dimensions) | 5g (5 ... 500 Hz / 2.5 h / X, Y, Z) |
| Weight per Piece (excluding packing) | 68.660 g |
| Housing material (Ambient conditions) | PA 6.6 |
| Operating current (Protective circuit) | 5 mA AC ... 1 A AC |
| Operating voltage (Protective circuit) | 5 V AC ... 250 V AC |
| Standby power consumption PC (General) | ≤ 20 mVA |
| Maximum continuous voltage UC (General) | 350 V AC |
| Mode of protection (Ambient conditions) | L-N |
| Switching function (Protective circuit) | N/C contact |
| Degree of pollution (Ambient conditions) | 2 |
| Voltage protection level Up(L-N) (General) | ≤ 2.5 kV |
| Voltage protection level Up(L-PE) (General) | ≤ 1.8 kV |
| Voltage protection level Up(N-PE) (General) | ≤ 1.8 kV |
| Ambient temperature (operation) (Dimensions) | -40 °C ... 85 °C |
| IEC power supply system (Ambient conditions) | TN-S |
| IEC test classification (Ambient conditions) | II |
| Short-circuit current rating ISCCR (General) | 1 kA |
| Max. backup fuse with branch wiring (General) | 63 A (MCB C) |
| Permissible humidity (operation) (Dimensions) | 5 % ... 95 % |
| Nominal discharge current In(8/20) µs (General) | 20 kA |
| Standards/regulations (Indicator/remote signaling) | IEC 61643-11 2011 |
| Surge protection fault message (Ambient conditions) | Remote indication contact |
| Ambient temperature (storage/transport) (Dimensions) | -40 °C ... 85 °C |
| Flammability rating according to UL 94 (Ambient conditions) | V-0 |
Technical specifications and performance data
Installation and operation guide