| Parameter | Value |
|---|---|
| GTIN | 4055626082028 |
| Note | Made to Order (non-returnable) |
| Orderkey | 2906495 |
| (General) | 1455 V AC (200 ms / safe failure mode) |
| Packing unit | 1 pc |
| Country of origin | DE (Germany) |
| Custom tariff number | 85363090 |
| (Ambient conditions) | N-PE |
| (Protective circuit) | N-G |
| Altitude (Dimensions) | ≤ 2000 m (amsl (above mean sea level)) |
| Type (Ambient conditions) | Male |
| Color (Ambient conditions) | jet black RAL 9005 |
| Depth (Key Commercial Data) | 51.7 mm |
| Width (Key Commercial Data) | 17.5 mm |
| EN type (Ambient conditions) | T3 |
| Height (Key Commercial Data) | 44.8 mm |
| Nominal voltage UN (General) | 230 V AC (TN-S) |
| SPD Type (Protective circuit) | 4CA |
| Combination wave UOC (General) | 6 kV |
| Nominal frequency fN (General) | 50 Hz (60 Hz) |
| Residual current IPE (General) | ≤ 5 µA |
| Rated load current IL (General) | 16 A AC (at 63 °C) |
| Response time tA(L-N) (General) | ≤ 25 ns |
| Response time tA(L-PE) (General) | ≤ 100 ns |
| Response time tA(N-PE) (General) | ≤ 100 ns |
| Degree of protection (Dimensions) | IP20 |
| TOV behavior at UT(L-N) (General) | 440 V AC (5 s / withstand mode) |
| Mounting type (Ambient conditions) | on base element |
| TOV behavior at UT(L-PE) (General) | 440 V AC (5 s / withstand mode) |
| TOV behavior at UT(N-PE) (General) | 1200 V AC (200 ms / safe failure mode) |
| Number of ports (Ambient conditions) | One |
| Weight per Piece (excluding packing) | 34.000 g |
| Housing material (Ambient conditions) | PA 6.6 |
| Reference test voltage UREF (General) | 255 V AC |
| Horizontal pitch (Key Commercial Data) | 1 Div. |
| Nominal frequency (Protective circuit) | 50/60 Hz |
| REACh SVHC (Standards and Regulations) | Lead 7439-92-1 |
| Standby power consumption PC (General) | ≤ 350 mVA |
| Maximum continuous voltage UC (General) | 255 V AC |
| Mode of protection (Ambient conditions) | L-N |
| Mode of protection (Protective circuit) | L-N |
| Degree of pollution (Ambient conditions) | 2 |
| Number of positions (Ambient conditions) | 2 |
| Voltage protection level Up(L-N) (General) | ≤ 1.25 kV |
| Voltage protection level Up(L-PE) (General) | ≤ 1.4 kV |
| Voltage protection level Up(N-PE) (General) | ≤ 1.4 kV |
| Ambient temperature (operation) (Dimensions) | -40 °C ... 80 °C |
| Short-circuit current rating ISCCR (General) | 1.5 kA AC |
| Standards/specifications (UL specifications) | EN 61643-11 2012 |
| Max. backup fuse with branch wiring (General) | 16 A (B) |
| Permissible humidity (operation) (Dimensions) | 5 % ... 95 % |
| Power distribution system (Protective circuit) | Single phase |
| Maximum backup fuse for through wiring (General) | 16 A (B) |
| Nominal discharge current In(8/20) µs (General) | 3 kA |
| Nominal discharge current In (Protective circuit) | 3 kA |
| Surge protection fault message (Ambient conditions) | optical |
| Ambient temperature (storage/transport) (Dimensions) | -40 °C ... 80 °C |
| Measured limiting voltage MLV (L-G) (Protective circuit) | 1200 V |
| Measured limiting voltage MLV (L-N) (Protective circuit) | 1500 V |
| Measured limiting voltage MLV (N-G) (Protective circuit) | 1200 V |
| Flammability rating according to UL 94 (Ambient conditions) | V-0 |
| Maximum continuous operating voltage MCOV (Protective circuit) | 255 V AC |