| Parameter | Value |
|---|---|
| GTIN | 4055626082073 |
| Note | Made to Order (non-returnable) |
| Orderkey | 2906489 |
| (General) | 1332 V AC (200 ms / safe failure mode) |
| Packing unit | 1 pc |
| Country of origin | DE (Germany) |
| (Connection data) | N-G |
| Custom tariff number | 85363010 |
| (Ambient conditions) | N-PE |
| (Protective circuit) | 1 A DC (30 V DC) |
| Altitude (Dimensions) | ≤ 2000 m (amsl (above mean sea level)) |
| Type (Ambient conditions) | DIN rail module, two-section, divisible |
| Color (Ambient conditions) | jet black RAL 9005 |
| SPD Type (Connection data) | 4CA |
| Depth (Key Commercial Data) | 65.5 mm |
| Width (Key Commercial Data) | 17.7 mm |
| EN type (Ambient conditions) | T3 |
| Height (Key Commercial Data) | 90 mm |
| Nominal voltage UN (General) | 120 V AC (TN-S) |
| Combination wave UOC (General) | 6 kV |
| Nominal frequency fN (General) | 50 Hz (60 Hz) |
| Residual current IPE (General) | ≤ 5 µA |
| Rated load current IL (General) | 16 A AC (at 63 °C) |
| Response time tA(L-N) (General) | ≤ 25 ns |
| Response time tA(L-PE) (General) | ≤ 100 ns |
| Response time tA(N-PE) (General) | ≤ 100 ns |
| Degree of protection (Dimensions) | IP20 |
| Screw thread (Protective circuit) | M3 |
| TOV behavior at UT(L-N) (General) | 175 V AC (5 s / withstand mode) |
| Mounting type (Ambient conditions) | DIN rail: 35 mm |
| TOV behavior at UT(L-PE) (General) | 240 V AC (5 s / withstand mode) |
| TOV behavior at UT(N-PE) (General) | 1200 V AC (200 ms / safe failure mode) |
| Nominal frequency (Connection data) | 50/60 Hz |
| Mode of protection (Connection data) | L-N |
| Number of ports (Ambient conditions) | One |
| Weight per Piece (excluding packing) | 77.100 g |
| Housing material (Ambient conditions) | PA 6.6 |
| Reference test voltage UREF (General) | 132 V AC |
| Stripping length (Protective circuit) | 8 mm |
| Tightening torque (UL specifications) | 5 lbf-in. ... 7 lbf-in. |
| Connection method (Protective circuit) | Screw connection |
| Horizontal pitch (Key Commercial Data) | 1 Div. |
| Operating current (Protective circuit) | 3 A AC |
| Operating voltage (Protective circuit) | 250 V AC |
| REACh SVHC (Standards and Regulations) | Lead 7439-92-1 |
| Standby power consumption PC (General) | ≤ 200 mVA |
| Tightening torque (Protective circuit) | 0.8 Nm |
| Maximum continuous voltage UC (General) | 150 V AC |
| Mode of protection (Ambient conditions) | L-N |
| Switching function (Protective circuit) | N/C contact |
| Degree of pollution (Ambient conditions) | 2 |
| Number of positions (Ambient conditions) | 2 |
| Screw thread (Indicator/remote signaling) | M3 |
| Voltage protection level Up(L-N) (General) | ≤ 0.75 kV |
| Power distribution system (Connection data) | Single phase |
| Voltage protection level Up(L-PE) (General) | ≤ 0.85 kV |
| Voltage protection level Up(N-PE) (General) | ≤ 0.85 kV |
| Ambient temperature (operation) (Dimensions) | -40 °C ... 80 °C |
| IEC power supply system (Ambient conditions) | TT |
| Short-circuit current rating ISCCR (General) | 1.5 kA AC |
| Max. backup fuse with branch wiring (General) | 16 A (B) |
| Permissible humidity (operation) (Dimensions) | 5 % ... 95 % |
| Standards/specifications (UL connection data) | EN 61643-11 2012 |
| Stripping length (Indicator/remote signaling) | 8 mm |
| Connection method (Indicator/remote signaling) | Screw connection |
| Nominal discharge current In (Connection data) | 3 kA |
| Tightening torque (Indicator/remote signaling) | 0.8 Nm |
| Conductor cross section AWG (UL specifications) | 14 ... 12 |
| Conductor cross section AWG (Protective circuit) | 24 ... 12 |
| Maximum backup fuse for through wiring (General) | 16 A (B) |
| Nominal discharge current In(8/20) µs (General) | 3 kA |
| Tightening torque (UL indicator/remote signaling) | 5 lbf-in. ... 7 lbf-in. |
| Conductor cross section solid (Protective circuit) | 0.2 mm² ... 4 mm² |
| Surge protection fault message (Ambient conditions) | Optical, remote indicator contact |
| Ambient temperature (storage/transport) (Dimensions) | -40 °C ... 80 °C |
| Conductor cross section flexible (Protective circuit) | 0.2 mm² ... 2.5 mm² |
| Measured limiting voltage MLV (L-G) (Connection data) | 700 V |
| Measured limiting voltage MLV (L-N) (Connection data) | 800 V |
| Measured limiting voltage MLV (N-G) (Connection data) | 700 V |
| Conductor cross section AWG (Indicator/remote signaling) | 24 ... 12 |
| Conductor cross section solid (Indicator/remote signaling) | 0.2 mm² ... 4 mm² |
| Conductor cross section AWG (UL indicator/remote signaling) | 14 ... 12 |
| Flammability rating according to UL 94 (Ambient conditions) | V-0 |
| Maximum continuous operating voltage MCOV (Connection data) | 150 V AC |
| Conductor cross section flexible (Indicator/remote signaling) | 0.2 mm² ... 2.5 mm² |
Technical specifications and performance data