| Parameter | Value |
|---|---|
| GTIN | 4055626257471 |
| Orderkey | 2907921 |
| (General) | ≤ 8.4 mVA (at UC) |
| Packing unit | 10 pc |
| Country of origin | DE (Germany) |
| (Connection data) | DC |
| (UL specifications) | EN 61643-11 2012 |
| Custom tariff number | 85363030 |
| (Ambient conditions) | PA 6.6-FR |
| (Protective circuit) | (DC+/DC-) - PE |
| Altitude (Dimensions) | ≤ 6000 m (amsl (above mean sea level)) |
| Type (Ambient conditions) | Male |
| Color (Ambient conditions) | light gray RAL 7035 |
| SPD Type (Connection data) | 4CA |
| Depth (Key Commercial Data) | 65.7 mm |
| Width (Key Commercial Data) | 17.5 mm |
| EN type (Ambient conditions) | T3 |
| Height (Key Commercial Data) | 46.7 mm |
| Nominal voltage UN (General) | 60 V AC (TN-S) |
| Combination wave UOC (General) | 4 kV |
| Nominal frequency fN (General) | 50 Hz (60 Hz) |
| Residual current IPE (General) | ≤ 5 µA |
| Shock (operation) (Dimensions) | 30g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z) |
| Response time tA(L-N) (General) | ≤ 25 ns |
| Response time tA(L-PE) (General) | ≤ 100 ns |
| Response time tA(N-PE) (General) | ≤ 100 ns |
| Degree of protection (Dimensions) | IP20 |
| Nominal voltage (Connection data) | 80 V DC |
| TOV behavior at UT(L-N) (General) | 120 V AC (120 min / safe failure mode) |
| Mounting type (Ambient conditions) | on base element |
| TOV behavior at UT(L-PE) (General) | 120 V AC (120 min / withstand mode) |
| Vibration (operation) (Dimensions) | 5g (5 ... 500 Hz / 2.5 h / X, Y, Z) |
| Nominal frequency (Connection data) | 50/60 Hz |
| Mode of protection (Connection data) | L-N |
| Number of ports (Ambient conditions) | One |
| Weight per Piece (excluding packing) | 33.160 g |
| Housing material (Ambient conditions) | PA 6.6-FR 20% GF |
| Reference test voltage UREF (General) | 66 V AC |
| Horizontal pitch (Key Commercial Data) | 1 Div. |
| Standby power consumption PC (General) | ≤ 5.3 mVA (at UREF) |
| Maximum continuous voltage UC (General) | 80 V AC |
| Mode of protection (Ambient conditions) | L-N |
| Mode of protection (Protective circuit) | (DC+) - (DC-) |
| Degree of pollution (Ambient conditions) | 2 |
| Number of positions (Ambient conditions) | 2 |
| Voltage protection level Up(L-N) (General) | ≤ 0.48 kV |
| Power distribution system (Connection data) | Single phase |
| Voltage protection level Up(L-PE) (General) | ≤ 0.8 kV |
| Voltage protection level Up(N-PE) (General) | ≤ 0.8 kV |
| Ambient temperature (operation) (Dimensions) | -40 °C ... 80 °C |
| IEC power supply system (Ambient conditions) | TN-S |
| Short-circuit current rating ISCCR (General) | 10 kA AC |
| Standards/specifications (UL specifications) | IEC 61643-11 2011 |
| Connection method (Additional technical data) | pluggable |
| Max. backup fuse with branch wiring (General) | 32 A (gG / B / C) |
| Permissible humidity (operation) (Dimensions) | 5 % ... 95 % |
| Nominal discharge current In (Connection data) | 3 kA |
| Nominal discharge current In(8/20) µs (General) | 2 kA |
| Maximum continuous voltage UC (Protective circuit) | 80 V DC |
| Surge protection fault message (Ambient conditions) | optical |
| Ambient temperature (storage/transport) (Dimensions) | -40 °C ... 80 °C |
| Measured limiting voltage MLV (L-G) (Connection data) | 680 V |
| Measured limiting voltage MLV (L-N) (Connection data) | 490 V |
| Measured limiting voltage MLV (N-G) (Connection data) | 680 V |
| Short-circuit current rating ISCCR (Protective circuit) | 0.25 kA DC (without additional backup fuse) |
| Flammability rating according to UL 94 (Ambient conditions) | V-0 |
| Maximum continuous operating voltage MCOV (Connection data) | 100 V AC |
| Maximum discharge current Imax(8/20) µs (Protective circuit) | 4 kA |
Technical specifications and performance data