| Parameter | Value |
|---|---|
| GTIN | 4017918065607 |
| Note | Made to Order (non-returnable) |
| Orderkey | 2763523 |
| (General) | C3 |
| Catalog page | Page 109 (TT-2002) |
| Packing unit | 5 pc |
| Country of origin | DE (Germany) |
| (Connection data) | E VDE 0845-3-1 |
| Custom tariff number | 85363010 |
| Rated current (General) | 300 mA |
| Type (Ambient conditions) | DIN rail module, one-piece |
| Color (Ambient conditions) | black |
| Depth (Key Commercial Data) | 54.9 mm |
| Width (Key Commercial Data) | 27.4 mm |
| (Standards and Regulations) | For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |
| Height (Key Commercial Data) | 77.5 mm |
| Resistance in series (General) | 4.7 Ω |
| VDE requirement class (General) | C2 |
| Degree of protection (Dimensions) | IP20 |
| IEC test classification (General) | C2 |
| Screw thread (Protective circuit) | M3 |
| Mounting type (Ambient conditions) | DIN rail: 35 mm |
| Weight per Piece (excluding packing) | 65.200 g |
| Response time tA(line-line) (General) | ≤ 1 ns |
| Stripping length (Protective circuit) | 8 mm |
| China RoHS (Standards and Regulations) | Environmentally Friendly Use Period = 50 |
| Connection method (Protective circuit) | Screw connection |
| REACh SVHC (Standards and Regulations) | Lead 7439-92-1 |
| Response time tA(line-earth) (General) | ≤ 100 ns |
| Tightening torque (Protective circuit) | 0.5 Nm ... 0.6 Nm |
| Maximum continuous voltage UC (General) | 24 V DC |
| Standards/regulations (Connection data) | Draft IEC 64644-1 |
| Direction of action (Ambient conditions) | Line-Line & Line-Earth Ground |
| Surge protection fault message (General) | none |
| Connection method IN (Protective circuit) | Screw terminal blocks |
| Connection method OUT (Protective circuit) | Screw terminal blocks |
| Residual voltage at In(line-line) (General) | ≤ 35 V |
| Ambient temperature (operation) (Dimensions) | -20 °C ... 60 °C |
| Operating effective current ICat UC (General) | ≤ 10 µA |
| Conductor cross section AWG (Protective circuit) | 24 ... 12 |
| Voltage protection level Up(line-line) (General) | ≤ 35 V |
| Voltage protection level Up(line-earth) (General) | ≤ 450 V |
| Conductor cross section solid (Protective circuit) | 0.2 mm² ... 4 mm² |
| Conductor cross section flexible (Protective circuit) | 0.2 mm² ... 2.5 mm² |
| Cut-off frequency fg (3 dB), sym. in 50 Ohm system (General) | 4 MHz |
| Cut-off frequency fg (3 dB), sym. in 600 Ohm system (General) | 300 kHz |
| Nominal discharge current In(8/20) µs (line-earth) (General) | 5 kA |
| Output voltage limitation at 1 kV/µs (line-line) spike (General) | ≤ 35 V |
| Output voltage limitation at 1 kV/µs (line-earth) spike (General) | ≤ 450 V |
| Output voltage limitation at 1 kV/µs (line-line) static (General) | ≤ 35 V |
| Output voltage limitation at 1 kV/µs (line-earth) static (General) | ≤ 450 V |
Technical specifications and performance data