| Parameter | Value |
|---|---|
| GTIN | 4017918104962 |
| Note | Made to Order (non-returnable) |
| Orderkey | 2749398 |
| (General) | 0.1 dB (up to 10 kHz 600 Ω system) |
| Catalog page | Page 100 (TT-2002) |
| Packing unit | 5 pc |
| Country of origin | DE (Germany) |
| (Connection data) | E VDE 0845-3-1 |
| Custom tariff number | 85363010 |
| Rated current (General) | 450 mA (25 °C) |
| Type (Ambient conditions) | DIN rail module, one-piece |
| Color (Ambient conditions) | black |
| Depth (Key Commercial Data) | 54.9 mm |
| Width (Key Commercial Data) | 47.6 mm |
| (Standards and Regulations) | For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |
| Height (Key Commercial Data) | 77.5 mm |
| Nominal voltage UN (General) | 5 V DC |
| Resistance in series (General) | 4.4 Ω |
| VDE requirement class (General) | C2 |
| Degree of protection (Dimensions) | IP20 |
| IEC test classification (General) | C2 |
| Screw thread (Protective circuit) | M3 |
| Mounting type (Ambient conditions) | DIN rail: 35 mm |
| Input attenuation aE, sym. (General) | typ. 0.1 dB (up to 40 kHz 150 Ω system) |
| Weight per Piece (excluding packing) | 102.420 g |
| Input attenuation aE, asym. (General) | 0.5 dB (up to 0.1 MHz 50 Ω system) |
| Response time tA(line-line) (General) | 1 ns |
| Stripping length (Protective circuit) | 8 mm |
| China RoHS (Standards and Regulations) | Environmentally Friendly Use Period = 50 |
| Connection method (Protective circuit) | Screw connection |
| REACh SVHC (Standards and Regulations) | Lead 7439-92-1 |
| Response time tA(line-earth) (General) | ≤ 100 ns |
| Maximum continuous voltage UC (General) | 5.8 V DC |
| Standards/regulations (Connection data) | Draft IEC 64644-1 |
| Direction of action (Ambient conditions) | Line-Line & Line-Signal Ground/Shield & Signal Ground/Shield-Earth Ground |
| Surge protection fault message (General) | none |
| Connection method IN (Protective circuit) | Screw terminal blocks |
| Connection method OUT (Protective circuit) | Screw terminal blocks |
| Residual voltage at In(line-line) (General) | ≤ 9 V |
| Ambient temperature (operation) (Dimensions) | -40 °C ... 80 °C |
| Operating effective current ICat UC (General) | ≤ 2 mA |
| Response time tA (line-signalground) (General) | ≤ 1 ns |
| Conductor cross section AWG (Protective circuit) | 24 ... 12 |
| Voltage protection level Up(line-line) (General) | ≤ 9 V |
| Voltage protection level Up(line-earth) (General) | ≤ 450 V |
| Conductor cross section solid (Protective circuit) | 0.2 mm² ... 4 mm² |
| Residual voltage at In(line-signalground) (General) | ≤ 9 V |
| Conductor cross section flexible (Protective circuit) | 0.2 mm² ... 2.5 mm² |
| Voltage protection level Up(line-signalground) (General) | ≤ 9 V |
| Nominal discharge current In(8/20) µs (line-line) (General) | 10 kA |
| Nominal discharge current In(8/20) µs (line-earth) (General) | 10 kA |
| Output voltage limitation at 1 kV/µs (line-line) spike (General) | ≤ 9 V |
| Output voltage limitation at 1 kV/µs (line-earth) spike (General) | ≤ 450 V |
| Output voltage limitation at 1 kV/µs (line-line) static (General) | ≤ 9 V |
| Cut-off frequency fg (3 dB), asym. (GND) in 50 Ohm system (General) | 600 kHz |
| Max. discharge current Imax(8/20) µs maximum (line-line) (General) | 10 kA |
| Output voltage limitation at 1 kV/µs (line-earth) static (General) | ≤ 450 V |
| Cut-off frequency fg (3 dB), asym. (GND) in 150 Ohm system (General) | 200 kHz |
| Cut-off frequency fg (3 dB), asym. (GND) in 600 Ohm system (General) | 50 kHz |
| Max. discharge current Imax(8/20) µs maximum (line-earth) (General) | 10 kA |
| Output voltage limitation at 1 kV/µs (line-signalground) static (General) | ≤ 9 V |
| Max. discharge current Imax(8/20) µs maximum (line-signalground) (General) | 10 kA |