| Parameter | Value |
|---|---|
| C2 | |
| Note | 2011 |
| Type | Attachment plug |
| Depth | 78 mm |
| Width | 63 mm |
| Height | 103 mm |
| EN type | T3 |
| Altitude | ≤ 2000 m (amsl) |
| Product type | Device protection |
| Mounting type | Plugging into the mains socket |
| Rated current | 150 mA (25 °C) |
| Product family | MAINTRAB |
| Number of ports | One |
| Housing material | PA 6 |
| Pollution degree | 2 |
| Connection method | RJ12 |
| Nominal voltage UN | 230/400 V AC (TN) |
| Dimensional drawing | |
| Direction of action | L/N-PE & Signal Line-Earth Ground |
| Insulating material | PA 6 |
| Capacity (Core-Core) | typ. 1 nF |
| Combination wave UOC | 4 kV |
| Degree of protection | IP20 (Child-proofing) |
| Nominal frequency fN | 50 Hz (60 Hz) |
| Overvoltage category | III |
| Residual current IPE | ≤ 5 µA |
| CTI value of material | 400 |
| Capacity (Core-Earth) | typ. 5 pF |
| Rated load current IL | 16 A (30 °C) |
| Response time tA(L-N) | ≤ 25 ns |
| Wire pairs per module | 1 |
| Response time tA(L-PE) | ≤ 100 ns |
| Response time tA(N-PE) | ≤ 100 ns |
| IEC test classification | C1 |
| TOV behavior at UT(L-N) | 335 V AC (5 s / withstand mode) |
| Standards/specifications | IEC 61643-11 |
| TOV behavior at UT(L-PE) | 440 V AC (5 s / withstand mode) |
| TOV behavior at UT(N-PE) | 1200 V AC (200 ms / safe failure mode) |
| Insulation resistance Riso | ≥ 1 MΩ |
| Max. required back-up fuse | 16 A (gG / B / C) |
| For country-specific use in | NL, E, I, S, FIN, TR |
| Reference test voltage UREF | 255 V AC |
| Response time tA(line-line) | ≤ 25 ns |
| Pulse reset time (line-line) | ≤ 15 ms |
| Response time tA(line-earth) | ≤ 100 ns |
| Standby power consumption PC | ≤ 1 VA |
| Energy absorption symmetrical | 140 J (L-N) |
| Maximum continuous voltage UC | 200 V DC |
| Enery absorption, asymmetrical | 220 J (L(N)-PE) |
| Surge protection fault message | optical |
| Ambient temperature (operation) | -25 °C ... 75 °C |
| Residual voltage at Iamax, (PE) | ≤ 1 kV (at 1 kA) |
| Permissible humidity (operation) | 5 % ... 95 % |
| Residual voltage at Iamax, (L-N) | ≤ 1 kV (at 1 kA) |
| Voltage protection level Up(L-N) | ≤ 1.2 kV |
| Residual voltage at Iamax, (L-PE) | ≤ 1 kV (at 1 kA) |
| Voltage protection level Up(L-PE) | ≤ 1.5 kV |
| Voltage protection level Up(N-PE) | ≤ 1.5 kV |
| Short-circuit current rating ISCCR | 1.5 kA AC |
| Max. backup fuse with branch wiring | 16 A (gG / B / C) |
| Operating effective current ICat UC | ≤ 150 µA |
| Max. discharge current Imax(8/20) µs | 2.5 kA |
| Flammability rating according to UL 94 | V-0 |
| Nominal discharge current In(8/20) µs | 3 kA (> 5x) |
| Voltage protection level Up(line-line) | ≤ 460 V (C2 - 1 kA) |
| Ambient temperature (storage/transport) | -25 °C ... 75 °C |
| Voltage protection level Up(line-earth) | ≤ 900 V (C2 - 2 kA) |
| Residual voltage at In(conductor-ground) | ≤ 30 V |
| Total discharge current Itotal(8/20) µs | 10 kA |
| Residual voltage at In(conductor-conductor) | ≤ 500 V |
| Maximum continuous operating voltage UC(L-N) | 275 V AC |
| Maximum continuous operating voltage UC(L-PE) | 360 V AC |
| Maximum continuous operating voltage UC(N-PE) | 360 V AC |
| Alternating current carrying capacity (line-line) | 250 mA - 1 s |
| Alternating current carrying capacity (line-earth) | 10 A - 1 s |
| Nominal discharge current In(8/20) µs (line-line) | 1 kA |
| Nominal pulse current Ian (10/1000) µs (line-line) | 35 A |
| Residual voltage with Ian (10/1000) µs (line-line) | ≤ 35 V |
| Cut-off frequency fg (3 dB), sym. in 100 Ω system | typ. 4 MHz |
| Cut-off frequency fg (3 dB), sym. in 150 Ω system | typ. 3 MHz |
| Cut-off frequency fg (3 dB), sym. in 600 Ω system | typ. 700 kHz |
| Nominal discharge current In(8/20) µs (line-ground) | 2.5 kA |
| Nominal pulse current Ian (10/1000) µs (line-earth) | 200 A |
| Residual voltage with Ian (10/1000) µs (line-earth) | ≤ 35 V |
| Output voltage limitation at 1 kV/µs (line-line) spike | ≤ 360 V |
| Output voltage limitation at 1 kV/µs (line-earth) spike | ≤ 900 V |
| Output voltage limitation at 1 kV/µs (line-line) static | ≤ 360 V |
Technical specifications and performance data
Installation and operation guide