| Parameter | Value |
|---|---|
| GTIN | 4055626774190 |
| Orderkey | 1074741 |
| (General) | 1455 V AC (200 ms / withstand mode) |
| Packing unit | 1 pc |
| Country of origin | DE (Germany) |
| (Connection data) | EN 61643-11 2012 |
| Custom tariff number | 85363090 |
| (Ambient conditions) | PC |
| Altitude (Dimensions) | ≤ 6000 m (amsl (above mean sea level)) |
| Type (Ambient conditions) | Busbar module, one-piece |
| Color (Ambient conditions) | light grey RAL 7035 |
| Response time tA (General) | ≤ 100 ns |
| Depth (Key Commercial Data) | 110.7 mm |
| Width (Key Commercial Data) | 47 mm |
| EN type (Ambient conditions) | T1 + T2 |
| Height (Key Commercial Data) | 223.2 mm |
| Nominal voltage UN (General) | 230/400 V AC (TN-S) |
| Nominal frequency fN (General) | 50 Hz (60 Hz) |
| Residual current IPE (General) | ≤ 5 µA |
| Degree of protection (Dimensions) | IP30 (Installed) |
| Screw thread (Protective circuit) | M5 |
| TOV behavior at UT(L-N) (General) | 337 V AC (5 s / withstand mode) |
| Mounting type (Ambient conditions) | Busbar 40 mm |
| TOV behavior at UT(L-PE) (General) | 442 V AC (120 min / withstand mode) |
| TOV behavior at UT(N-PE) (General) | 1200 V AC (200 ms / withstand mode) |
| Weight per Piece (excluding packing) | 829.800 g |
| Housing material (Ambient conditions) | PA 6.6-FR |
| Stripping length (Protective circuit) | 18 mm |
| Connection method (Protective circuit) | Screw terminal blocks |
| Horizontal pitch (Key Commercial Data) | 2.6 Div. |
| REACh SVHC (Standards and Regulations) | Lead 7439-92-1 |
| Tightening torque (Protective circuit) | 4.5 Nm |
| Maximum continuous voltage UC (General) | 255 V AC |
| Mode of protection (Ambient conditions) | L-N |
| Standards/regulations (Connection data) | IEC 61643-11 2011 |
| Degree of pollution (Ambient conditions) | 2 |
| Number of positions (Ambient conditions) | 4 |
| Voltage protection level Up(L-N) (General) | ≤ 1.5 kV |
| Voltage protection level Up(L-PE) (General) | ≤ 2 kV |
| Voltage protection level Up(N-PE) (General) | ≤ 1.5 kV |
| Ambient temperature (operation) (Dimensions) | -40 °C ... 80 °C |
| IEC power supply system (Ambient conditions) | TN-S |
| IEC test classification (Ambient conditions) | I + II |
| Short-circuit current rating ISCCR (General) | 25 kA |
| Max. backup fuse with branch wiring (General) | 250 A (gG) |
| Permissible humidity (operation) (Dimensions) | 5 % ... 95 % |
| Conductor cross section solid (Protective circuit) | 2.5 mm² ... 35 mm² |
| Follow current interrupt rating Ifi(L-N) (General) | 25 kA |
| Follow current interrupt rating Ifi(L-PE) (General) | 25 kA |
| Follow current interrupt rating Ifi(N-PE) (General) | 100 A |
| Surge protection fault message (Ambient conditions) | optical |
| Ambient temperature (storage/transport) (Dimensions) | -40 °C ... 80 °C |
| Conductor cross section flexible (Protective circuit) | 2.5 mm² ... 35 mm² |
| Nominal discharge current In(8/20) µs (L-N) (General) | 20 kA |
| Nominal discharge current In(8/20) µs (L-PE) (General) | 20 kA |
| Nominal discharge current In(8/20) µs (N-PE) (General) | 80 kA |
| Flammability rating according to UL 94 (Ambient conditions) | V-0 |
| Impulse discharge current (10/350) µs (L-N), charge (General) | 3.75 As |
| Impulse discharge current (10/350) µs (L-PE), charge (General) | 3.75 As |
| Impulse discharge current (10/350) µs (N-PE), charge (General) | 15 As |
| Impulse discharge current (10/350) µs (L-N), specific energy (General) | 15 kJ/Ω |
| Impulse discharge current (10/350) µs (L-PE), specific energy (General) | 15 kJ/Ω |
| Impulse discharge current (10/350) µs (N-PE), specific energy (General) | 225 kJ/Ω |
| Impulse discharge current (10/350) µs (L-N), peak current value Iimp (General) | 7.5 kA |
| Impulse discharge current (10/350) µs (L-PE), peak current value Iimp (General) | 7.5 kA |
| Impulse discharge current (10/350) µs (N-PE), peak current value Iimp (General) | 30 kA |