Service time: Monday to Friday 9:00-18:00
FLT-SEC-P-T1-N/PE-350/100-FM - FLT-SEC-P-T1-N/PE-350/100-FM 2905472 FLT‐CP‐N/PE‐350 2859754 PHOENIX CONTACT Combination type 1/2 protective..
In Stock Hot Product

FLT-SEC-P-T1-N/PE-350/100-FM

FLT-SEC-P-T1-N/PE-350/100-FM 2905472 FLT‐CP‐N/PE‐350 2859754 PHOENIX CONTACT Combination type 1/2 protective..

$0.00USD
4893 in stock
Key Specifications
GTIN:4046356950701
Orderkey:2905472
(General):≤ 0.8 kV (at 3 kA)
Catalog page:Page 33 (C-4-2017)
Supplier Information
Products: 0
Usually ships within 2-3 business days
Quality Guaranteed
Fast Shipping
Technical Support

Technical Specifications

ParameterValue
GTIN4046356950701
Orderkey2905472
(General)≤ 0.8 kV (at 3 kA)
Catalog pagePage 33 (C-4-2017)
Packing unit1 pc
Country of originDE (Germany)
Custom tariff number85363030
(Ambient conditions)PBT-FR
(Protective circuit)1 A DC (30 V DC)
(UL connection data)EN 61643-11 2012
Altitude (Dimensions)≤ 2000 m (amsl (above mean sea level))
Type (Ambient conditions)DIN rail module, two-section, divisible
Color (Ambient conditions)light grey RAL 7035
Response time tA (General)≤ 100 ns
SPD Type (Connection data)2CA
Depth (Key Commercial Data)74.5 mm
Width (Key Commercial Data)35.6 mm
(Standards and Regulations)For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”
EN type (Ambient conditions)T1 / T2
Height (Key Commercial Data)95.2 mm
Nominal voltage UN (General)240 V AC (TN - only N-PE)
TOV behavior at UT (General)1200 V AC (200 ms / withstand mode)
Nom. voltage (Connection data)240 V AC
Nominal frequency fN (General)50 Hz (60 Hz)
Residual current IPE (General)≤ 0.01 mA
Shock (operation) (Dimensions)30g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z)
Rated load current IL (General)125 A (< 55 °C)
Residual voltage Ures (General)≤ 1.5 kV (at In)
Degree of protection (Dimensions)IP20 (only when all terminal points are used)
Screw thread (Protective circuit)M2
Mounting type (Ambient conditions)DIN rail: 35 mm
Vibration (operation) (Dimensions)5g (5 - 500 Hz/2.5 h/X, Y, Z)
Nominal frequency (Connection data)50/60 Hz
Mode of protection (Connection data)N-G
Weight per Piece (excluding packing)380.200 g
Housing material (Ambient conditions)PA 6.6-FR 20% GF
Operating current (UL specifications)1 A AC
Operating voltage (UL specifications)125 V AC
Stripping length (Protective circuit)7 mm
Tightening torque (UL specifications)4 lbf-in.
Voltage protection level Up (General)≤ 1.5 kV
China RoHS (Standards and Regulations)Environmentally Friendly Use Period = 50
Connection method (Protective circuit)Plug-in/screw connection via COMBICON
Horizontal pitch (Key Commercial Data)2 Div.
Operating current (Protective circuit)10 mA AC ... 1 A AC
Operating voltage (Protective circuit)12 V AC ... 250 V AC
REACh SVHC (Standards and Regulations)2-(2H-benzotriazol-2-yl)-4,6-ditertpentylphenol (UV-328) 25973-55-1
Tightening torque (Protective circuit)0.25 Nm
Maximum continuous voltage UC (General)350 V AC
Mode of protection (Ambient conditions)N-PE
Switching function (Protective circuit)PDT contact
Degree of pollution (Ambient conditions)2
Number of positions (Ambient conditions)1
Screw thread (Indicator/remote signaling)M5
Standards/regulations (UL connection data)IEC 61643-11 2011
Power distribution system (Connection data)Single phase
Ambient temperature (operation) (Dimensions)-40 °C ... 80 °C
IEC power supply system (Ambient conditions)TN-S
IEC test classification (Ambient conditions)I / II
Follow current interrupt rating Ifi (General)100 A
Permissible humidity (operation) (Dimensions)5 % ... 95 %
Stripping length (Indicator/remote signaling)18 mm
Connection method (Indicator/remote signaling)Fork-type cable lug
Nominal discharge current In (Connection data)20 kA
Tightening torque (Indicator/remote signaling)4.5 Nm
Conductor cross section AWG (UL specifications)30 ... 14
Voltage protection rating VPR (Connection data)1200 V
Conductor cross section AWG (Protective circuit)28 ... 16
Nominal discharge current In(8/20) µs (General)100 kA
Tightening torque (UL indicator/remote signaling)40 lbf-in.
Conductor cross section solid (Protective circuit)0.14 mm² ... 1.5 mm²
Surge protection fault message (Ambient conditions)Optical, remote indicator contact
Ambient temperature (storage/transport) (Dimensions)-40 °C ... 80 °C
Conductor cross section flexible (Protective circuit)0.14 mm² ... 1.5 mm²
Conductor cross section AWG (Indicator/remote signaling)13 ... 2
Impulse discharge current (10/350) µs, charge (General)50 As
Conductor cross section solid (Indicator/remote signaling)2.5 mm² ... 35 mm²
Conductor cross section AWG (UL indicator/remote signaling)3 ... 2
Flammability rating according to UL 94 (Ambient conditions)V-0
Maximum continuous operating voltage MCOV (Connection data)350 V AC
Conductor cross section flexible (Indicator/remote signaling)1.5 mm² ... 16 mm²
Front of wave sparkover voltage at 6 kV (1.2/50) µs (General)≤ 1.5 kV
Impulse discharge current (10/350) µs, peak value limp (General)100 kA
Impulse discharge current (10/350) µs, specific energy (General)2500 kJ/Ω

Product Description

Plug-in lightning current arrester according to type 1/class I, for use in power grids between N and PE.
Key Features
  • Industrial grade quality
  • RoHS compliant
  • CE certified
  • 1-year warranty

Product Documents

Datasheet

Technical specifications and performance data

User Manual

Installation and operation guide

Top