Service time: Monday to Friday 9:00-18:00
FLT-SEC-P-T1-3C-350/25-FM - FLT-SEC-P-T1-3C-350/25-FM 2905419 FLT‐CP‐PLUS‐3C‐350 2882653 PHOENIX CONTACT Combination type 1/2 protective..
In Stock Hot Product

FLT-SEC-P-T1-3C-350/25-FM

FLT-SEC-P-T1-3C-350/25-FM 2905419 FLT‐CP‐PLUS‐3C‐350 2882653 PHOENIX CONTACT Combination type 1/2 protective..

$0.00USD
4775 in stock
Key Specifications
:SPD according to AS/NZS 1768 Cat. C3
Note:Max. single impulse: 100 kA (8/20 µs)
Type:DIN rail module, two-section, divisible
Depth:74.5 mm (incl. DIN rail 7.5 mm)
Supplier Information
Products: 0
Usually ships within 2-3 business days
Quality Guaranteed
Fast Shipping
Technical Support

Technical Specifications

ParameterValue
SPD according to AS/NZS 1768 Cat. C3
NoteMax. single impulse: 100 kA (8/20 µs)
TypeDIN rail module, two-section, divisible
Depth74.5 mm (incl. DIN rail 7.5 mm)
Width106.8 mm
Height95.2 mm
EN typeT1 / T2
Altitude≤ 2000 m (amsl)
SPD Type2CA
Product typeCombination type
Screw threadM5
Mounting typeDIN rail: 35 mm
Material groupI
Product familySEC Family
Connection nameRemote fault indicator contact
Nominal voltage240 V AC
Open side panelNo
Article revision12
Horizontal pitch6 Div.
Housing materialPA 6.6-FR 20 % GF
Pollution degree2
Response time tA≤ 100 ns
Stripping length18 mm
Connection methodScrew connection
Nominal frequency50/60 Hz
Operating current10 mA AC ... 1 A AC
Operating voltage12 V AC ... 250 V AC
Shock (operation)30g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z)
Tightening torque4.5 Nm
Mode of protectionL-PEN
Nominal voltage UN240/415 V AC (TN-C)
Switching functionChangeover contact
TOV behavior at UT415 V AC (5 s / withstand mode)
Dimensional drawing
Direction of action3L-PEN
Insulating materialPA6.6-FR 20% GF
Number of positions3
AC operating current1 A AC
Color (Base element)gray (RAL 7042)
Degree of protectionIP20 (only when all terminal points are used)
Nominal frequency fN50 Hz (60 Hz)
Overvoltage categoryIII
CTI value of material600
Rated load current IL125 A (< 55 °C)
Residual voltage Ures≤ 1.5 kV (at In)
Vibration (operation)5g (5 - 500 Hz/2.5 h/X, Y, Z)
Color (Male connector)light gray (RAL 7035)
IEC power supply systemTN-C
IEC test classificationI / II
Standards/specificationsIEC 61643-11
Power distribution systemDelta
Conductor cross section AWG13 ... 2
Voltage protection level Up≤ 1.5 kV
Nominal discharge current In20 kA
Conductor cross section rigid2.5 mm² ... 35 mm²
Maximum continuous voltage UC350 V AC
Surge protection fault messageOptical, remote indicator contact
Ambient temperature (operation)-40 °C ... 80 °C
Conductor cross section flexible2.5 mm² ... 35 mm²
Permissible humidity (operation)5 % ... 95 %
Short-circuit current rating ISCCR50 kA
Follow current interrupt rating Ifi50 kA
Max. backup fuse with branch wiring315 A (gG)
Short-circuit current rating (SCCR)50 kA
Voltage protection rating VPR (L-G)1500 V
Voltage protection rating VPR (L-L)2000 V
Flammability rating according to UL 94V-0
Nominal discharge current In(8/20) µs25 kA
Ambient temperature (storage/transport)-40 °C ... 80 °C
Maximum discharge current Imax(8/20) µs50 kA
Max. backup fuse with V-type through wiring125 A (gG)
Total discharge current Itotal(10/350) µs75 kA
Impulse discharge current (10/350) µs, charge12.5 As
Maximum continuous operating voltage MCOV (L-G)350 V AC
Maximum continuous operating voltage MCOV (L-L)700 V AC
Front of wave sparkover voltage at 6 kV (1.2/50) µs≤ 1.5 kV
Impulse discharge current (10/350) µs, peak value limp25 kA
Impulse discharge current (10/350) µs, specific energy160 kJ/Ω

Product Description

Plug-in lightning current arrester, according to type 1/class I, for three-phase power grids with combined PE and N routing in one conductor (L1, L2, L3, PEN).
Key Features
  • Industrial grade quality
  • RoHS compliant
  • CE certified
  • 1-year warranty

Product Documents

Datasheet

Technical specifications and performance data

User Manual

Installation and operation guide

Top