Key Specifications
GTIN:4055626176437
Orderkey:2907260
(General):1640 V AC (200 ms / safe failure mode)
Catalog page:Page 28 (C-4-2017)
Supplier Information
Products: 0
Usually ships within 2-3 business days
Quality Guaranteed
Fast Shipping
Technical Support

Technical Specifications

ParameterValue
GTIN4055626176437
Orderkey2907260
(General)1640 V AC (200 ms / safe failure mode)
Catalog pagePage 28 (C-4-2017)
Packing unit1 pc
Country of originDE (Germany)
(Connection data)EN 61643-11 2012
Custom tariff number85363030
(Ambient conditions)PBT-FR
(Protective circuit)1 A DC (30 V DC)
Altitude (Dimensions)≤ 2000 m (amsl (above mean sea level))
Type (Ambient conditions)DIN rail module, two-section, divisible
Color (Ambient conditions)light grey RAL 7035
Response time tA (General)≤ 100 ns
Depth (Key Commercial Data)74.5 mm
Width (Key Commercial Data)106.8 mm
(Standards and Regulations)Lead 7439-92-1
EN type (Ambient conditions)T1 / T2
Height (Key Commercial Data)167 mm
Nominal voltage UN (General)400/690 V AC (TN-C)
TOV behavior at UT (General)580 V AC (5 s / withstand mode)
Nominal frequency fN (General)50 Hz (60 Hz)
Residual current IPE (General)≤ 5 µA
Residual voltage Ures (General)≤ 2.5 kV (at In)
Degree of protection (Dimensions)IP20 (only when all terminal points are used)
Screw thread (Protective circuit)M2
Mounting type (Ambient conditions)DIN rail: 35 mm
Weight per Piece (excluding packing)1,755.000 g
Housing material (Ambient conditions)PA 6.6-FR 20% GF
Stripping length (Protective circuit)7 mm
Voltage protection level Up (General)≤ 2.5 kV
Connection method (Protective circuit)Plug-in/screw connection via COMBICON
Horizontal pitch (Key Commercial Data)6 Div.
Operating current (Protective circuit)10 mA AC ... 1 A AC
Operating voltage (Protective circuit)12 V AC ... 250 V AC
REACh SVHC (Standards and Regulations)N,N-dimethylacetamide 127-19-5
Tightening torque (Protective circuit)0.25 Nm
Maximum continuous voltage UC (General)440 V AC
Mode of protection (Ambient conditions)L-PEN
Standards/regulations (Connection data)IEC 61643-11 2011
Switching function (Protective circuit)PDT contact
Degree of pollution (Ambient conditions)2
Number of positions (Ambient conditions)3
Screw thread (Indicator/remote signaling)M5
Ambient temperature (operation) (Dimensions)-40 °C ... 80 °C
IEC power supply system (Ambient conditions)TN-C
IEC test classification (Ambient conditions)I / II
Short-circuit current rating ISCCR (General)50 kA
Follow current interrupt rating Ifi (General)50 kA
Permissible humidity (operation) (Dimensions)5 % ... 95 %
Stripping length (Indicator/remote signaling)18 mm
Connection method (Indicator/remote signaling)Fork-type cable lug
Tightening torque (Indicator/remote signaling)4.5 Nm
Conductor cross section AWG (Protective circuit)28 ... 16
Nominal discharge current In(8/20) µs (General)25 kA
Conductor cross section solid (Protective circuit)0.14 mm² ... 1.5 mm²
Maximum discharge current Imax(8/20) µs (General)50 kA
Surge protection fault message (Ambient conditions)Optical, remote indicator contact
Ambient temperature (storage/transport) (Dimensions)-40 °C ... 80 °C
Conductor cross section flexible (Protective circuit)0.14 mm² ... 1.5 mm²
Conductor cross section AWG (Indicator/remote signaling)13 ... 2
Impulse discharge current (10/350) µs, charge (General)12.5 As
Conductor cross section solid (Indicator/remote signaling)2.5 mm² ... 35 mm²
Flammability rating according to UL 94 (Ambient conditions)V-0
Conductor cross section flexible (Indicator/remote signaling)1.5 mm² ... 16 mm²
Front of wave sparkover voltage at 6 kV (1.2/50) µs (General)≤ 2.5 kV
Impulse discharge current (10/350) µs, peak value limp (General)25 kA
Impulse discharge current (10/350) µs, specific energy (General)160 kJ/Ω

Product Description

Plug-in lightning current arrester, according to type 1/class I, with fuse resistant to momentary overcurrents, for three-phase power supply networks with PE and N placed in combination on one conduct
Key Features
  • Industrial grade quality
  • RoHS compliant
  • CE certified
  • 1-year warranty

Product Documents