| Parameter | Value |
|---|---|
| GTIN | 4055626012032 |
| Note | Made to Order (non-returnable) |
| Orderkey | 2905968 |
| (General) | 460 V AC (120 min / withstand mode) |
| Catalog page | Page 28 (C-4-2017) |
| Packing unit | 1 pc |
| Country of origin | DE (Germany) |
| (Connection data) | EN 61643-11 2012 |
| Custom tariff number | 85363030 |
| (Ambient conditions) | PBT-FR |
| Altitude (Dimensions) | ≤ 4000 m (amsl (above mean sea level)) |
| Type (Ambient conditions) | Male |
| Color (Ambient conditions) | light grey RAL 7035 |
| Response time tA (General) | ≤ 100 ns |
| Depth (Key Commercial Data) | 64.2 mm |
| Width (Key Commercial Data) | 35.5 mm |
| EN type (Ambient conditions) | T1 / T2 |
| Height (Key Commercial Data) | 113.4 mm |
| Nominal voltage UN (General) | 240 V AC (TN) |
| TOV behavior at UT (General) | 415 V AC (5 s / withstand mode) |
| Nominal frequency fN (General) | 50 Hz (60 Hz) |
| Residual voltage Ures (General) | ≤ 1.5 kV (at In) |
| Degree of protection (Dimensions) | IP20 |
| Mounting type (Ambient conditions) | on base element |
| Weight per Piece (excluding packing) | 335.780 g |
| Housing material (Ambient conditions) | PA 6.6-FR 20% GF |
| Voltage protection level Up (General) | ≤ 1.5 kV |
| Horizontal pitch (Key Commercial Data) | 2 Div. |
| REACh SVHC (Standards and Regulations) | Lead 7439-92-1 |
| Maximum continuous voltage UC (General) | 264 V AC |
| Mode of protection (Ambient conditions) | L-PEN |
| Standards/regulations (Connection data) | IEC 61643-11 2011 |
| Degree of pollution (Ambient conditions) | 2 |
| Number of positions (Ambient conditions) | 1 |
| Ambient temperature (operation) (Dimensions) | -40 °C ... 80 °C |
| IEC power supply system (Ambient conditions) | TN-C |
| IEC test classification (Ambient conditions) | I / II |
| Short-circuit current rating ISCCR (General) | 50 kA |
| Connection method (Additional technical data) | pluggable |
| Follow current interrupt rating Ifi (General) | 50 kA |
| Permissible humidity (operation) (Dimensions) | 5 % ... 95 % |
| Nominal discharge current In(8/20) µs (General) | 25 kA |
| Maximum continuous voltage UC (Protective circuit) | 275 V AC |
| Maximum discharge current Imax(8/20) µs (General) | 50 kA |
| Surge protection fault message (Ambient conditions) | optical |
| Ambient temperature (storage/transport) (Dimensions) | -40 °C ... 80 °C |
| Short-circuit current rating ISCCR (Protective circuit) | 100 kA |
| Follow current interrupt rating Ifi (Protective circuit) | 100 kA |
| Impulse discharge current (10/350) µs, charge (General) | 12.5 As |
| Flammability rating according to UL 94 (Ambient conditions) | V-0 |
| Maximum discharge current Imax(8/20) µs (Protective circuit) | 100 kA (AS NZS 1768:2007) |
| Front of wave sparkover voltage at 6 kV (1.2/50) µs (General) | ≤ 1.5 kV |
| Impulse discharge current (10/350) µs, peak value limp (General) | 25 kA |
| Impulse discharge current (10/350) µs, specific energy (General) | 160 kJ/Ω |
Technical specifications and performance data