| Parameter | Value |
|---|---|
| GTIN | 4055626176000 |
| Orderkey | 2907259 |
| (General) | 1640 V AC (200 ms / safe failure mode) |
| Catalog page | Page 28 (C-4-2017) |
| Packing unit | 1 pc |
| Country of origin | DE (Germany) |
| (Connection data) | EN 61643-11 2012 |
| Custom tariff number | 85363030 |
| (Ambient conditions) | PBT-FR |
| (Protective circuit) | 1 A DC (30 V DC) |
| Altitude (Dimensions) | ≤ 2000 m (amsl (above mean sea level)) |
| Type (Ambient conditions) | DIN rail module, two-section, divisible |
| Color (Ambient conditions) | light grey RAL 7035 |
| Response time tA (General) | ≤ 100 ns |
| Depth (Key Commercial Data) | 74.5 mm |
| Width (Key Commercial Data) | 35.5 mm |
| (Standards and Regulations) | Lead 7439-92-1 |
| EN type (Ambient conditions) | T1 / T2 |
| Height (Key Commercial Data) | 167 mm |
| Nominal voltage UN (General) | 400 V AC (TN) |
| TOV behavior at UT (General) | 580 V AC (5 s / withstand mode) |
| Nominal frequency fN (General) | 50 Hz (60 Hz) |
| Residual current IPE (General) | ≤ 5 µA |
| Residual voltage Ures (General) | ≤ 2.5 kV (at In) |
| Degree of protection (Dimensions) | IP20 (only when all terminal points are used) |
| Screw thread (Protective circuit) | M2 |
| Mounting type (Ambient conditions) | DIN rail: 35 mm |
| Weight per Piece (excluding packing) | 660.000 g |
| Housing material (Ambient conditions) | PA 6.6-FR 20% GF |
| Stripping length (Protective circuit) | 7 mm |
| Voltage protection level Up (General) | ≤ 2.5 kV |
| Connection method (Protective circuit) | Plug-in/screw connection via COMBICON |
| Horizontal pitch (Key Commercial Data) | 2 Div. |
| Operating current (Protective circuit) | 10 mA AC ... 1 A AC |
| Operating voltage (Protective circuit) | 12 V AC ... 250 V AC |
| REACh SVHC (Standards and Regulations) | N,N-dimethylacetamide 127-19-5 |
| Tightening torque (Protective circuit) | 0.25 Nm |
| Maximum continuous voltage UC (General) | 440 V AC |
| Mode of protection (Ambient conditions) | L-N |
| Standards/regulations (Connection data) | IEC 61643-11 2011 |
| Switching function (Protective circuit) | PDT contact |
| Degree of pollution (Ambient conditions) | 2 |
| Number of positions (Ambient conditions) | 1 |
| Screw thread (Indicator/remote signaling) | M5 |
| Ambient temperature (operation) (Dimensions) | -40 °C ... 80 °C |
| IEC power supply system (Ambient conditions) | TN-C |
| IEC test classification (Ambient conditions) | I / II |
| Short-circuit current rating ISCCR (General) | 50 kA |
| Follow current interrupt rating Ifi (General) | 50 kA |
| Permissible humidity (operation) (Dimensions) | 5 % ... 95 % |
| Stripping length (Indicator/remote signaling) | 18 mm |
| Connection method (Indicator/remote signaling) | Fork-type cable lug |
| Tightening torque (Indicator/remote signaling) | 4.5 Nm |
| Conductor cross section AWG (Protective circuit) | 28 ... 16 |
| Nominal discharge current In(8/20) µs (General) | 25 kA |
| Conductor cross section solid (Protective circuit) | 0.14 mm² ... 1.5 mm² |
| Maximum discharge current Imax(8/20) µs (General) | 50 kA |
| Surge protection fault message (Ambient conditions) | Optical, remote indicator contact |
| Ambient temperature (storage/transport) (Dimensions) | -40 °C ... 80 °C |
| Conductor cross section flexible (Protective circuit) | 0.14 mm² ... 1.5 mm² |
| Conductor cross section AWG (Indicator/remote signaling) | 13 ... 2 |
| Impulse discharge current (10/350) µs, charge (General) | 12.5 As |
| Conductor cross section solid (Indicator/remote signaling) | 2.5 mm² ... 35 mm² |
| Flammability rating according to UL 94 (Ambient conditions) | V-0 |
| Conductor cross section flexible (Indicator/remote signaling) | 1.5 mm² ... 16 mm² |
| Front of wave sparkover voltage at 6 kV (1.2/50) µs (General) | ≤ 2.5 kV |
| Impulse discharge current (10/350) µs, peak value limp (General) | 25 kA |
| Impulse discharge current (10/350) µs, specific energy (General) | 160 kJ/Ω |