| Parameter | Value |
|---|---|
| GTIN | 4046356045520 |
| Note | Made to Order (non-returnable) |
| Orderkey | 2859913 |
| (General) | 457 V AC (120 min / withstand mode) |
| Catalog page | Page 28 (C-6-2013) |
| Packing unit | 10 pc |
| Country of origin | DE (Germany) |
| Custom tariff number | 85363010 |
| (Ambient conditions) | L-PEN |
| Altitude (Dimensions) | ≤ 2000 m (amsl (above mean sea level)) |
| Type (Ambient conditions) | Male |
| Color (Ambient conditions) | gray/blue |
| Response time tA (General) | ≤ 100 ns |
| Depth (Key Commercial Data) | 56.4 mm |
| Width (Key Commercial Data) | 35.45 mm |
| EN type (Ambient conditions) | T1 / T2 |
| Height (Key Commercial Data) | 46.6 mm |
| Nominal voltage UN (General) | 240 V AC (TN) |
| TOV behavior at UT (General) | 415 V AC (5 s / withstand mode) |
| SPD Type (Protective circuit) | 4CA |
| Nominal frequency fN (General) | 50 Hz (60 Hz) |
| Shock (operation) (Dimensions) | 25g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z) |
| Residual voltage Ures (General) | ≤ 1.5 kV (at In) |
| Degree of protection (Dimensions) | IP20 |
| Nom. voltage (Protective circuit) | 240 V AC |
| Mounting type (Ambient conditions) | on base element |
| Vibration (operation) (Dimensions) | 5g (5 - 500 Hz/2.5 h/X, Y, Z) |
| Weight per Piece (excluding packing) | 249.650 g |
| Housing material (Ambient conditions) | PBT |
| Voltage protection level Up (General) | ≤ 1.5 kV |
| Horizontal pitch (Key Commercial Data) | 2 Div. |
| Nominal frequency (Protective circuit) | 50/60 Hz |
| Maximum continuous voltage UC (General) | 350 V AC |
| Mode of protection (Ambient conditions) | L-N |
| Mode of protection (Protective circuit) | L-N |
| Degree of pollution (Ambient conditions) | 2 |
| Number of positions (Ambient conditions) | 1 |
| Ambient temperature (operation) (Dimensions) | -40 °C ... 80 °C |
| IEC power supply system (Ambient conditions) | TT |
| IEC test classification (Ambient conditions) | I / II |
| Short-circuit current rating ISCCR (General) | 50 kA |
| Follow current interrupt rating Ifi (General) | 50 kA |
| Max. backup fuse with branch wiring (General) | 315 A (gG) |
| Permissible humidity (operation) (Dimensions) | 5 % ... 95 % |
| Power distribution system (Protective circuit) | Split phase |
| Nominal discharge current In(8/20) µs (General) | 25 kA |
| Maximum discharge current Imax(8/20) µs (General) | 50 kA |
| Surge protection fault message (Ambient conditions) | optical |
| Ambient temperature (storage/transport) (Dimensions) | -40 °C ... 80 °C |
| Nominal discharge current In(L-N) (Protective circuit) | 20 kA |
| Impulse discharge current (10/350) µs, charge (General) | 12.5 As |
| Measured limiting voltage MLV (L-N) (Protective circuit) | 1350 V |
| Flammability rating according to UL 94 (Ambient conditions) | V-0 |
| Front of wave sparkover voltage at 6 kV (1.2/50) µs (General) | ≤ 1.5 kV |
| Impulse discharge current (10/350) µs, peak value limp (General) | 25 kA |
| Impulse discharge current (10/350) µs, specific energy (General) | 160 kJ/Ω |
| Maximum continuous operating voltage MCOV (L-N) (Protective circuit) | 264 V AC |