| Parameter | Value |
|---|---|
| T1 + T2 | |
| Note | 2011 |
| Type | DIN rail module, two-section, divisible |
| Depth | 71.5 mm |
| Width | 71.2 mm |
| Height | 95 mm |
| Altitude | ≤ 2000 m (amsl) |
| SPD Type | 4CA |
| Product type | Arrester combination |
| Screw thread | M5 |
| Mounting type | DIN rail: 35 mm |
| Material group | I |
| Connection name | Remote fault indicator contact |
| Nominal voltage | 240/415 V AC |
| Open side panel | No |
| Horizontal pitch | 4 Div. |
| Housing material | PBT |
| Pollution degree | 2 |
| Response time tA | ≤ 25 ns |
| Stripping length | 18 mm |
| Connection method | Screw terminal blocks |
| Nominal frequency | 50/60 Hz |
| Operating current | 10 mA AC ... 1 A AC |
| Operating voltage | 12 V AC ... 250 V AC |
| Shock (operation) | 25g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z) |
| Tightening torque | 4.5 Nm |
| Mode of protection | L-PEN |
| Nominal voltage UN | 240/415 V AC (TN-C) |
| Switching function | Changeover contact |
| TOV behavior at UT | 415 V AC (5 s / withstand mode) |
| Dimensional drawing | |
| Direction of action | 2L-N/PE |
| Insulating material | PA 6.6/PBT |
| Number of positions | 2 |
| AC operating current | 1 A AC |
| Degree of protection | IP20 (only when all terminal points are used) |
| Follow current (N-G) | 10 kA (264 V AC) |
| Nominal frequency fN | 50 Hz (60 Hz) |
| Overvoltage category | III |
| CTI value of material | 600 |
| Rated load current IL | 125 A (< 55 °C) |
| Residual voltage Ures | ≤ 1.5 kV (at In) |
| Standards/regulations | DIN VDE 0110-1 / IEC 60664-1 / IEC 61643-1 |
| Vibration (operation) | 5g (5 - 500 Hz/2.5 h/X, Y, Z) |
| IEC power supply system | TN-C |
| IEC test classification | I + II |
| Standards/specifications | IEC 61643-11 |
| Power distribution system | Delta |
| Conductor cross section AWG | 13 ... 2 |
| Voltage protection level Up | ≤ 1.5 kV |
| Conductor cross section rigid | 2.5 mm² ... 35 mm² |
| Maximum continuous voltage UC | 350 V AC |
| Surge protection fault message | Optical, remote indicator contact |
| Ambient temperature (operation) | -40 °C ... 80 °C |
| Conductor cross section flexible | 2.5 mm² ... 25 mm² |
| Permissible humidity (operation) | 5 % ... 95 % |
| Nominal discharge current In(L-G) | 20 kA |
| Nominal discharge current In(L-L) | 20 kA |
| Short-circuit current rating ISCCR | 25 kA (264 V AC) |
| Follow current interrupt rating Ifi | 25 kA (264 V AC) |
| Max. backup fuse with branch wiring | 315 A (gG) |
| Measured limiting voltage MLV (L-G) | 1340 V |
| Measured limiting voltage MLV (L-L) | 2450 V |
| Flammability rating according to UL 94 | V - 0 |
| Nominal discharge current In(8/20) µs | 25 kA |
| Ambient temperature (storage/transport) | -40 °C ... 80 °C |
| Max. backup fuse with V-type through wiring | 125 A (gG) |
| Impulse discharge current (10/350) µs, charge | 12.5 As |
| Maximum continuous operating voltage MCOV (L-G) | 264 V AC |
| Maximum continuous operating voltage MCOV (L-L) | 528 V AC |
| Front of wave sparkover voltage at 6 kV (1.2/50) µs | ≤ 1.5 kV |
| Impulse discharge current (10/350) µs, peak value limp | 25 kA |
| Impulse discharge current (10/350) µs, specific energy | 160 kJ/Ω |
Technical specifications and performance data