| Parameter | Value |
|---|---|
| GTIN | 4046356909471 |
| Note | Made to Order (non-returnable) |
| Orderkey | 2801637 |
| Packing unit | 1 pc |
| Country of origin | DE (Germany) |
| (Connection data) | EN 61643-11 2012 |
| Custom tariff number | 85363030 |
| (Ambient conditions) | TN-S |
| Altitude (Dimensions) | ≤ 2000 m (amsl (above mean sea level)) |
| Type (Ambient conditions) | DIN rail module, one-piece |
| (Additional descriptions) | 230/400 V AC (TT - only N-PE) |
| Color (Ambient conditions) | jet black RAL 9005 |
| Depth (Key Commercial Data) | 66.2 mm |
| Width (Key Commercial Data) | 17.6 mm |
| EN type (Ambient conditions) | T1 |
| Height (Key Commercial Data) | 88.6 mm |
| Degree of protection (Dimensions) | IP20 (only when all terminal points are used) |
| Screw thread (Protective circuit) | M5 |
| Mounting type (Ambient conditions) | DIN rail: 35 mm |
| Weight per Piece (excluding packing) | 188.000 g |
| Housing material (Ambient conditions) | PA 6.6 |
| Stripping length (Protective circuit) | 14.5 mm |
| Connection method (Protective circuit) | Screw terminal blocks |
| Horizontal pitch (Key Commercial Data) | 1 Div. |
| Tightening torque (Protective circuit) | 4.5 Nm |
| Mode of protection (Ambient conditions) | N-PE |
| Standards/regulations (Connection data) | IEC 61643-11 2011 |
| Degree of pollution (Ambient conditions) | 2 |
| Number of positions (Ambient conditions) | 1 |
| Response time tA (Additional descriptions) | ≤ 100 ns |
| Ambient temperature (operation) (Dimensions) | -40 °C ... 85 °C |
| IEC power supply system (Ambient conditions) | TT |
| IEC test classification (Ambient conditions) | I |
| Nominal voltage UN (Additional descriptions) | 230/400 V AC (TN - only N-PE) |
| TOV behavior at UT (Additional descriptions) | 1200 V AC (200 ms / withstand mode) |
| Permissible humidity (operation) (Dimensions) | 5 % ... 95 % |
| Nominal frequency fN (Additional descriptions) | 50 Hz (60 Hz) |
| Residual current IPE (Additional descriptions) | ≤ 0.5 mA |
| Rated load current IL (Additional descriptions) | 80 A |
| Conductor cross section AWG (Protective circuit) | 6 ... 2 |
| Conductor cross section solid (Protective circuit) | 2.5 mm² ... 35 mm² |
| Surge protection fault message (Ambient conditions) | none |
| Ambient temperature (storage/transport) (Dimensions) | -40 °C ... 85 °C |
| Conductor cross section flexible (Protective circuit) | 2.5 mm² ... 25 mm² |
| Voltage protection level Up (Additional descriptions) | ≤ 4 kV |
| Standby power consumption PC (Additional descriptions) | ≤ 130 mVA |
| Maximum continuous voltage UC (Additional descriptions) | 260 V AC |
| Flammability rating according to UL 94 (Ambient conditions) | V-0 |
| Follow current interrupt rating Ifi (Additional descriptions) | 100 A (260 V AC) |
| Nominal discharge current In(8/20) µs (Additional descriptions) | 50 kA |
| Impulse discharge current (10/350) µs, charge (Additional descriptions) | 25 As |
| Front of wave sparkover voltage at 6 kV (1.2/50) µs (Additional descriptions) | ≤ 4 kV |
| Impulse discharge current (10/350) µs, peak value limp (Additional descriptions) | 50 kA |
| Impulse discharge current (10/350) µs, specific energy (Additional descriptions) | 625 kJ/Ω |
Technical specifications and performance data
Installation and operation guide