| Parameter | Value |
|---|---|
| GTIN | 4046356479929 |
| Orderkey | 2800106 |
| (General) | 440 V AC (120 min / withstand mode) |
| Catalog page | Page 22 (TT-2011) |
| Packing unit | 1 pc |
| Country of origin | DE (Germany) |
| (Connection data) | EN 61643-11 2012 |
| Custom tariff number | 85363010 |
| (Ambient conditions) | TT |
| Altitude (Dimensions) | ≤ 2000 m (amsl (above mean sea level)) |
| Type (Ambient conditions) | DIN rail module, one-piece |
| Color (Ambient conditions) | black |
| Depth (Key Commercial Data) | 65.5 mm |
| Width (Key Commercial Data) | 17.7 mm |
| (Standards and Regulations) | No hazardous substances above threshold values |
| EN type (Ambient conditions) | T1 |
| Height (Key Commercial Data) | 90 mm |
| Nominal voltage UN (General) | 230/400 V AC (TN) |
| Nominal frequency fN (General) | 50 Hz (60 Hz) |
| Residual current IPE (General) | ≤ 0.1 mA |
| Rated load current IL (General) | 80 A |
| Degree of protection (Dimensions) | IP20 (only when all terminal points are used) |
| Response time tA(L-PEN) (General) | ≤ 100 ns |
| Screw thread (Protective circuit) | M5 |
| Mounting type (Ambient conditions) | DIN rail: 35 mm |
| TOV behavior at UT(L-PEN) (General) | 440 V AC (5 s / withstand mode) |
| Weight per Piece (excluding packing) | 180.200 g |
| Housing material (Ambient conditions) | PA 6.6 |
| Stripping length (Protective circuit) | 14.5 mm |
| China RoHS (Standards and Regulations) | Environmentally friendly use period: unlimited = EFUP-e |
| Connection method (Protective circuit) | Screw connection |
| Horizontal pitch (Key Commercial Data) | 1 Div. |
| Standby power consumption PC (General) | ≤ 44 mVA |
| Tightening torque (Protective circuit) | 4.5 Nm |
| Mode of protection (Ambient conditions) | L-PEN |
| Standards/regulations (Connection data) | IEC 61643-11 2011 |
| Degree of pollution (Ambient conditions) | 2 |
| Number of positions (Ambient conditions) | 1 |
| Ambient temperature (operation) (Dimensions) | -40 °C ... 85 °C |
| IEC power supply system (Ambient conditions) | TN-S |
| IEC test classification (Ambient conditions) | I |
| Short-circuit current rating ISCCR (General) | 2.5 kA |
| Voltage protection level Up(L-PEN) (General) | ≤ 5 kV |
| Max. backup fuse with branch wiring (General) | 250 A AC (gG) |
| Permissible humidity (operation) (Dimensions) | 5 % ... 95 % |
| Conductor cross section AWG (Protective circuit) | 6 ... 2 |
| Surge protection fault message (Ambient conditions) | none |
| Ambient temperature (storage/transport) (Dimensions) | -40 °C ... 85 °C |
| Follow current interrupt rating Ifi(L-PEN) (General) | 2.5 kA |
| Max. backup fuse with V-type through wiring (General) | 80 A AC (gG) |
| Conductor cross section solid max. (Protective circuit) | 35 mm² |
| Conductor cross section solid min. (Protective circuit) | 2.5 mm² |
| Maximum continuous operating voltage UC(L-PEN) (General) | 440 V AC |
| Nominal discharge current In(8/20) µs (L-PEN) (General) | 25 kA |
| Conductor cross section flexible max. (Protective circuit) | 25 mm² |
| Conductor cross section flexible min. (Protective circuit) | 2.5 mm² |
| Flammability rating according to UL 94 (Ambient conditions) | V-0 |
| Front of wave sparkover voltage at 6 kV (1.2/50) µs (General) | ≤ 5 kV |
| Impulse discharge current (10/350) µs (L-PEN), charge (General) | 12.5 As |
| Impulse discharge current (10/350) µs (L-PEN), specific energy (General) | 156 kJ/Ω |
| Impulse discharge current (10/350) µs (L-PEN), peak current value Iimp (General) | 25 kA |
Technical specifications and performance data
Installation and operation guide