| Parameter | Value |
|---|---|
| T1 / T2 | |
| Note | 2011 |
| Type | DIN rail module, two-section, divisible |
| Color | black (RAL 9005) |
| Depth | 67.3 mm |
| Width | 17.7 mm |
| Height | 47 mm |
| EN type | T1 / T2 |
| Altitude | ≤ 2000 m (amsl) |
| SPD Type | 4CA |
| Product type | Replacement plug |
| Mounting type | on base element |
| Material group | I |
| Product family | VALVETRAB MS |
| Article revision | 05 |
| Horizontal pitch | 1 Div. |
| Housing material | PA 6.6 |
| Pollution degree | 2 |
| Response time tA | ≤ 100 ns |
| Connection method | pluggable |
| Nominal frequency | 50/60 Hz |
| Shock (operation) | 30g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z) |
| Mode of protection | N-PE |
| Nominal voltage UN | 240/415 V AC (TN-S) |
| TOV behavior at UT | 1200 V AC (200 ms / withstand mode) |
| Dimensional drawing | |
| Direction of action | N-PE |
| Insulating material | PA 6.6/PBT |
| Number of positions | 1 |
| Degree of protection | IP20 |
| Nominal frequency fN | 50 Hz (60 Hz) |
| Overvoltage category | III |
| Residual current IPE | ≤ 5 µA |
| CTI value of material | 600 |
| Residual voltage Ures | ≤ 0.6 kV (at In) |
| Vibration (operation) | 7.5g (10 ... 500 Hz / 2.5 h / X, Y, Z) |
| IEC power supply system | TN-S |
| IEC test classification | I / II |
| Standards/specifications | IEC 61643-11 |
| Power distribution system | Single phase |
| Voltage protection level Up | ≤ 1.7 kV |
| Standby power consumption PC | ≤ 1.3 mVA |
| Maximum continuous voltage UC | 264 V AC |
| Surge protection fault message | optical |
| Ambient temperature (operation) | -40 °C ... 80 °C |
| Permissible humidity (operation) | 5 % ... 95 % |
| Nominal discharge current In(N-G) | 20 kA |
| Follow current interrupt rating Ifi | 100 A (264 V AC) |
| Measured limiting voltage MLV (N-G) | 2600 V |
| Flammability rating according to UL 94 | V-0 |
| Nominal discharge current In(8/20) µs | 50 kA |
| Ambient temperature (storage/transport) | -40 °C ... 80 °C |
| Maximum discharge current Imax(8/20) µs | 50 kA |
| Impulse discharge current (10/350) µs, charge | 25 As |
| Maximum continuous operating voltage MCOV (N-G) | 264 V AC |
| Front of wave sparkover voltage at 6 kV (1.2/50) µs | ≤ 1.7 kV |
| Impulse discharge current (10/350) µs, peak value limp | 50 kA |
| Impulse discharge current (10/350) µs, specific energy | 625 kJ/Ω |
Technical specifications and performance data
Installation and operation guide