Key Specifications
GTIN:4017918163648
Orderkey:2817990
(General):≤ 0.1 kV (at 3 kA)
Catalog page:Page 63 (C-4-2017)
Supplier Information
Products: 0
Usually ships within 2-3 business days
Quality Guaranteed
Fast Shipping
Technical Support

Technical Specifications

ParameterValue
GTIN4017918163648
Orderkey2817990
(General)≤ 0.1 kV (at 3 kA)
Catalog pagePage 63 (C-4-2017)
Packing unit10 pc
Country of originDE (Germany)
(UL specifications)EN 61643-11 2012
Custom tariff number85363010
(Ambient conditions)TT
Altitude (Dimensions)≤ 2000 m (amsl (above mean sea level))
Type (Ambient conditions)Male
Color (Ambient conditions)jet black RAL 9005
Response time tA (General)≤ 100 ns
SPD Type (Connection data)4CA
Depth (Key Commercial Data)55.3 mm
Width (Key Commercial Data)17.5 mm
EN type (Ambient conditions)T2
Height (Key Commercial Data)52.4 mm
Nominal voltage UN (General)240/415 V AC (TN - only N-PE)
TOV behavior at UT (General)1200 V AC (200 ms / withstand mode)
Nominal frequency fN (General)50 Hz (60 Hz)
Residual current IPE (General)≤ 5 µA
Shock (operation) (Dimensions)25g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z)
Residual voltage Ures (General)≤ 0.4 kV (at In)
Degree of protection (Dimensions)IP20
Mounting type (Ambient conditions)on base element
Vibration (operation) (Dimensions)5g (10 ... 500 Hz / 2.5 h / X, Y, Z)
Nominal frequency (Connection data)50/60 Hz
Mode of protection (Connection data)N-G
Weight per Piece (excluding packing)35.560 g
Housing material (Ambient conditions)PA 6.6
Voltage protection level Up (General)≤ 1.5 kV
Connection method (Protective circuit)pluggable
Horizontal pitch (Key Commercial Data)1 Div.
Standby power consumption PC (General)≤ 1.5 mVA
Maximum continuous voltage UC (General)260 V AC
Mode of protection (Ambient conditions)N-PE
Degree of pollution (Ambient conditions)2
Number of positions (Ambient conditions)1
Standards/regulations (UL specifications)IEC 61643-11 2011
Power distribution system (Connection data)Single phase
Ambient temperature (operation) (Dimensions)-40 °C ... 80 °C
IEC power supply system (Ambient conditions)TN
IEC test classification (Ambient conditions)II
Follow current interrupt rating Ifi (General)100 A (260 V)
Permissible humidity (operation) (Dimensions)5 % ... 95 %
Nominal discharge current In(8/20) µs (General)20 kA
Maximum discharge current Imax(8/20) µs (General)40 kA
Nominal discharge current In(N-G) (Connection data)20 kA
Surge protection fault message (Ambient conditions)optical
Ambient temperature (storage/transport) (Dimensions)-40 °C ... 80 °C
Measured limiting voltage MLV (N-G) (Connection data)1490 V
Flammability rating according to UL 94 (Ambient conditions)V-0
Front of wave sparkover voltage at 6 kV (1.2/50) µs (General)≤ 1.5 kV
Maximum continuous operating voltage MCOV (N-G) (Connection data)260 V AC
Arrester can be tested with CHECKMASTER from software version: (Ambient conditions)From SW rev. 1.10

Product Description

Plug-in protection against type 2 surges, with N-PE sum current arc arrester, for base element.
Key Features
  • Industrial grade quality
  • RoHS compliant
  • CE certified
  • 1-year warranty

Product Documents

Datasheet

Technical specifications and performance data

User Manual

Installation and operation guide

Top