| Parameter | Value |
|---|---|
| GTIN | 4055626394589 |
| Note | Made to Order (non-returnable) |
| Orderkey | 2909844 |
| (General) | At altitudes > 2000 m (amsl), a lateral distance of 2 mm must be maintained between live and grounded parts. |
| Packing unit | 1 pc |
| Country of origin | DE (Germany) |
| (Connection data) | EN 61643-11 2012 |
| Custom tariff number | 85363010 |
| (Ambient conditions) | T2 |
| Altitude (Dimensions) | ≤ 5000 m (amsl (above mean sea level)) |
| Minimum order quantity | 10 pc |
| Type (Ambient conditions) | DIN rail module, two-section, divisible |
| (Additional descriptions) | 60 Hz |
| Color (Ambient conditions) | jet black RAL 9005 |
| Depth (Key Commercial Data) | 55.3 mm |
| Width (Key Commercial Data) | 17.5 mm |
| EN type (Ambient conditions) | T2 |
| Height (Key Commercial Data) | 52.4 mm |
| Shock (operation) (Dimensions) | 25g |
| Degree of protection (Dimensions) | IP20 |
| Mounting type (Ambient conditions) | on base element |
| Vibration (operation) (Dimensions) | 5g |
| Weight per Piece (excluding packing) | 32.610 g |
| Housing material (Ambient conditions) | PA 6.6 |
| Connection method (Protective circuit) | pluggable |
| Horizontal pitch (Key Commercial Data) | 1 Div. |
| Mode of protection (Ambient conditions) | L-PE (for IT systems without N in series with a VAL-MS plug) |
| Standards/regulations (Connection data) | IEC 61643-11 2011 |
| Degree of pollution (Ambient conditions) | 2 |
| Number of positions (Ambient conditions) | 1 |
| Response time tA (Additional descriptions) | ≤ 100 ns |
| Ambient temperature (operation) (Dimensions) | -40 °C ... 80 °C |
| IEC test classification (Ambient conditions) | II |
| Permissible humidity (operation) (Dimensions) | 5 % ... 95 % |
| Nominal frequency fN (Additional descriptions) | 50 Hz |
| Residual current IPE (Additional descriptions) | ≤ 3 µA |
| Surge protection fault message (Ambient conditions) | optical |
| Ambient temperature (storage/transport) (Dimensions) | -40 °C ... 80 °C |
| Voltage protection level Up (Additional descriptions) | ≤ 3 kV |
| Maximum continuous voltage UC (Additional descriptions) | 260 V AC |
| Flammability rating according to UL 94 (Ambient conditions) | V-0 |
| Short-circuit current rating ISCCR (Additional descriptions) | 25 kA (in series with a VAL-MS plug) |
| Nominal discharge current In(8/20) µs (Additional descriptions) | 20 kA |
| Maximum discharge current Imax(8/20) µs (Additional descriptions) | 40 kA |
| Front of wave sparkover voltage at 6 kV (1.2/50) µs (Additional descriptions) | ≤ 3 kV |
Technical specifications and performance data