| Parameter | Value |
|---|---|
| GTIN | 4046356328029 |
| Orderkey | 0903026 |
| (General) | 18 V DC ... 32 V DC |
| Catalog page | Page 326 (C-4-2017) |
| Packing unit | 6 pc |
| Fuse (General) | electronic |
| Country of origin | DE (Germany) |
| (Connection data) | UL 1604 |
| Fuse type (General) | Automatic device |
| Custom tariff number | 85362010 |
| Depth (Electrical data) | 80 mm |
| Width (Electrical data) | 12.5 mm |
| Height (Electrical data) | 83 mm |
| Color (Key Commercial Data) | black |
| Operating voltage (General) | 24 V DC |
| (Standards and Regulations) | For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |
| Nominal current IN (General) | 4 A |
| Degree of pollution (General) | 2 |
| Dielectric strength (General) | max. 32 V DC (Load circuit) |
| Rated surge voltage (General) | 0.5 kV |
| Required backup fuse (General) | not required, integrated failsafe element |
| Switching capacity ICN (General) | Active current limitation |
| Degree of protection (Dimensions) | IP20 (Housing) |
| Height NS 35/15 (Electrical data) | 90.5 mm |
| Screw thread (Ambient conditions) | M4 |
| Height NS 35/7,5 (Electrical data) | 83 mm |
| Mounting type (Key Commercial Data) | DIN rail: 35 mm |
| Weight per Piece (excluding packing) | 69.020 g |
| Stripping length (Ambient conditions) | 10 mm |
| China RoHS (Standards and Regulations) | Environmentally Friendly Use Period = 50 |
| Connection method (Ambient conditions) | Screw connection |
| REACh SVHC (Standards and Regulations) | Lead 7439-92-1 |
| Closed-circuit current range I0 (General) | typ. 25 mA ±5 mA (When switched on) |
| Standards/specifications (Connection data) | UL 508 |
| Tightening torque max (Ambient conditions) | 1.2 Nm |
| Ambient temperature (operation) (Dimensions) | 0 °C ... 50 °C (non-condensing) |
| Installation instructions (Key Commercial Data) | When mounted in rows without convection cooling, the nominal device current should only be led to a maximum of 80% due to the thermal effect during continuous operation (100% operating factor).Special precautionary measures must be taken in systems or machines, to prevent components from restarting (e.g., use of a safety PLC).Parallel connection of multiple circuit breakers is not permitted. |
| Conductor cross section AWG max. (Ambient conditions) | 6 |
| Conductor cross section AWG min. (Ambient conditions) | 20 |
| Conductor cross section solid max. (Ambient conditions) | 16 mm² |
| Conductor cross section solid min. (Ambient conditions) | 0.5 mm² |
| Conductor cross section flexible max. (Ambient conditions) | 16 mm² |
| Conductor cross section flexible min. (Ambient conditions) | 0.5 mm² |
| Flammability rating according to UL 94 (Key Commercial Data) | V0 |
| 2 conductors with same cross section, solid max. (Ambient conditions) | 4 mm² |
| 2 conductors with same cross section, solid min. (Ambient conditions) | 0.5 mm² |
| 2 conductors with same cross section, stranded max. (Ambient conditions) | 4 mm² |
| 2 conductors with same cross section, stranded min. (Ambient conditions) | 0.5 mm² |
| Conductor cross section flexible, with ferrule with plastic sleeve max. (Ambient conditions) | 10 mm² |
| Conductor cross section flexible, with ferrule with plastic sleeve min. (Ambient conditions) | 0.5 mm² |
| Conductor cross section flexible, with ferrule without plastic sleeve max. (Ambient conditions) | 10 mm² |
| Conductor cross section flexible, with ferrule without plastic sleeve min. (Ambient conditions) | 0.5 mm² |
| 2 conductors with same cross section, stranded, ferrules without plastic sleeve, max. (Ambient conditions) | 2.5 mm² |
| 2 conductors with same cross section, stranded, ferrules without plastic sleeve, min. (Ambient conditions) | 0.5 mm² |
| 2 conductors with same cross section, stranded, TWIN ferrules with plastic sleeve, max. (Ambient conditions) | 6 mm² |
| 2 conductors with same cross section, stranded, TWIN ferrules with plastic sleeve, min. (Ambient conditions) | 0.5 mm² |
Technical specifications and performance data
Installation and operation guide