| Parameter | Value |
|---|---|
| 18 V DC ... 32 V DC | |
| Fuse | electronic |
| Note | No. 14 |
| Type | DIN rail module, one-piece |
| Color | black (RAL 9005) |
| Depth | 80 mm |
| Width | 12.5 mm |
| Height | 83 mm |
| General | When mounted in rows without convection cooling, the nominal device current should only be led to a maximum of 80% due to the thermal effect during continuous operation (100% operating factor).Special precautionary measures must be taken in systems or machines, to prevent components from restarting (e.g., use of a safety PLC).Parallel connection of multiple circuit breakers is not permitted. |
| Voltage | < 3 V DC (Low state) |
| Fuse type | Automatic device |
| Switch off | typ. 1.8 x IN |
| Product type | Device circuit breakers |
| Pulse length | min. 10 ms |
| Screw thread | M4 |
| Voltage drop | 130 mV (at IN) |
| Humidity test | 96 h, 95 % RH, 40 °C |
| Input voltage | max. 32 V DC |
| Mounting type | DIN rail: 35 mm |
| Output current | max. 0.2 A (Short-circuit-proof) |
| Output voltage | 24 V DC |
| Product family | EC-E |
| Connection name | Auxiliary contact |
| Height NS 35/15 | 90.5 mm |
| No. of channels | 1 |
| Switch-on delay | typ. 0.5 s |
| Tripping method | E (electronic) |
| Article revision | 02 |
| Height NS 35/7,5 | 83 mm |
| Stripping length | 10 mm |
| Connection method | Screw connection |
| Cross section AWG | 26 ... 6 (converted acc. to IEC) |
| Operating voltage | 24 V DC |
| Tightening torque | ... 1.2 Nm |
| Nominal current IN | 6 A |
| Switching function | Reset input |
| Current consumption | typ. 2.6 mA (at 24 V DC) |
| Degree of pollution | 2 |
| Dielectric strength | max. 32 V DC (Load circuit) |
| Number of positions | 1 |
| Rated surge voltage | 0.5 kV |
| Degree of protection | IP20 (Housing) |
| Max. capacitive load | 20000 µF |
| Required backup fuse | not required, integrated failsafe element |
| Nominal cross section | 16.00 mm² |
| Switching capacity ICN | Active current limitation |
| Standards/specifications | UL 508 |
| Active current limitation | active |
| MTBF (IEC 61709, SN 29500) | 7430000 h (at 25 °C with 80 % load) |
| Conductor cross section AWG | 20 ... 6 |
| Conductor cross section rigid | 0.5 mm² ... 16 mm² |
| Ambient temperature (operation) | 0 °C ... 50 °C (non-condensing) |
| Closed-circuit current range I0 | typ. 25 mA ±5 mA (When switched on) |
| Conductor cross section flexible | 0.5 mm² ... 16 mm² |
| Flammability rating according to UL 94 | V0 |
| Ambient temperature (storage/transport) | -20 °C ... 70 °C |
| Conductor cross section, flexible [AWG] | 20 ... 6 (converted acc. to IEC) |
| 2 conductors with same cross section, solid | 0.5 mm² ... 4 mm² |
| 2 conductors with same cross section, flexible | 0.5 mm² ... 4 mm² |
| 2 conductors with the same cross-section AWG rigid | 20 ... 12 (converted acc. to IEC) |
| 2 conductors with the same cross-section AWG flexible | 20 ... 12 (converted acc. to IEC) |
| Flexible conductor cross section (ferrule with plastic sleeve) | 0.5 mm² ... 10 mm² |
| Conductor cross-section flexible (ferrule without plastic sleeve) | 0.5 mm² ... 10 mm² |
| Conductor cross section, flexible, with ferrule, with plastic sleeve | 0.5 mm² ... 10 mm² |
| Conductor cross section flexible, with ferrule without plastic sleeve | 0.5 mm² ... 10 mm² |
| 2 conductors with same cross section, flexible, with ferrule without plastic sleeve | 0.5 mm² ... 2.5 mm² |
| 2 conductors with the same cross section, flexible, with TWIN ferrule with plastic sleeve | 0.5 mm² ... 6 mm² |
Technical specifications and performance data
Installation and operation guide