| Parameter | Value |
|---|---|
| C1 | |
| Note | 2002 |
| Type | Attachment plug for DIN rail mounting |
| Color | silver-colored |
| Depth | 63.5 mm |
| Width | 25 mm |
| Height | 102 mm |
| Product type | Surge protection for information technology |
| Mounting type | Connection-specific attachment plug and DIN rail, 35 mm |
| Rated current | ≤ 1.5 A (25 °C) |
| Product family | DATATRAB |
| Open side panel | No |
| Housing material | Zinc die-cast |
| Pollution degree | 2 |
| Connection method | RJ45 |
| Dimensional drawing | |
| Direction of action | Line-Line & Line-Ground/Shield |
| Number of positions | 8 |
| Capacity (Core-Core) | typ. 12 pF (f= 1 MHz / VR= 0 V) |
| Degree of protection | IP20 |
| Overvoltage category | II |
| Residual current IPE | ≤ 400 µA |
| Capacity (Core-Earth) | typ. 2 pF (f= 1 MHz / VR= 0 V) |
| Wire pairs per module | 4 |
| IEC test classification | B2 |
| Standards/specifications | IEC 61643-21 |
| Input attenuation aE, sym. | ≤ 1 dB (up to100 MHz/direct measuring) |
| Response time tA(line-line) | ≤ 1 ns |
| Response time tA(line-earth) | ≤ 100 ns |
| Impulse durability (line-line) | B2 - 1 kV / 25 A |
| Near-end crosstalk attenuation | ≥ 35 dB (250 MHz/100 Ω/link) |
| Surge protection fault message | none |
| Ambient temperature (operation) | -40 °C ... 70 °C |
| Impulse durability (line-earth) | B2 - 4 kV / 100 A |
| Permissible humidity (operation) | 5 % ... 85 % |
| Operating effective current ICat UC | ≤ 1 µA |
| Voltage protection level Up(line-line) | ≤ 9 V (B2 - 1 kV / 25 A) |
| Ambient temperature (storage/transport) | -40 °C ... 70 °C |
| Voltage protection level Up(line-earth) | ≤ 900 V (B2 - 4 kV / 100 A) |
| Maximum continuous voltage UC(line-line) | ≤ 3.3 V DC (±60 V DC/PoE+) |
| Total discharge current Itotal(8/20) µs | 10 kA |
| Residual voltage at In(conductor-conductor) | ≤ 15 V |
| Nominal discharge current In(8/20) µs (line-line) | 100 A |
| Nominal pulse current Ian (10/700) µs (line-line) | ≤ 40 A |
| Nominal pulse current Ian (10/700) µs (line-earth) | ≤ 160 A |
| Nominal discharge current In(8/20) µs (line-ground) | 2 kA (per signal pair) |
| Output voltage limitation at 1 kV/µs (line-line) spike | ≤ 85 V (PoE) |
| Output voltage limitation at 1 kV/µs (line-earth) spike | ≤ 700 V |
| Output voltage limitation at 1 kV/µs (line-line) static | ≤ 9 V |
| Output voltage limitation at 1 kV/µs (line-earth) static | ≤ 700 V |
Technical specifications and performance data