| Parameter | Value |
|---|---|
| GTIN | 4046356151900 |
| Orderkey | 2881007 |
| (General) | D1 - 1 kA |
| Catalog page | Page 142 (C-4-2017) |
| Packing unit | 1 pc |
| Country of origin | DE (Germany) |
| Custom tariff number | 85363010 |
| Rated current (General) | ≤ 1.5 A (25 °C) |
| Type (Ambient conditions) | Attachment plug for DIN rail mounting |
| Color (Ambient conditions) | silver/black |
| Depth (Key Commercial Data) | 63.5 mm |
| Width (Key Commercial Data) | 25 mm |
| (Standards and Regulations) | No hazardous substances above threshold values |
| Height (Key Commercial Data) | 102 mm |
| Capacity (line-line) (General) | typ. 12 pF (f= 1 MHz / VR= 0 V) |
| Residual current IPE (General) | ≤ 400 µA |
| Capacity (line-earth) (General) | typ. 2 pF (f= 1 MHz / VR= 0 V) |
| Degree of protection (Dimensions) | IP20 |
| IEC test classification (General) | B2 |
| Mounting type (Ambient conditions) | Connection-specific attachment plug and DIN rail, 35 mm |
| Connection method (Connection data) | DIN rail NS35 |
| (Connection, equipotential bonding) | ISO/IEC 11801-Am.1 2006 |
| Input attenuation aE, sym. (General) | ≤ 1 dB (up to100 MHz/direct measuring) |
| Weight per Piece (excluding packing) | 314.100 g |
| Housing material (Ambient conditions) | Zinc die-cast |
| Response time tA(line-line) (General) | ≤ 1 ns |
| China RoHS (Standards and Regulations) | Environmentally friendly use period: unlimited = EFUP-e |
| Connection method (Protective circuit) | RJ45 |
| Response time tA(line-earth) (General) | ≤ 100 ns |
| Direction of action (Ambient conditions) | Line-Line & Line-Ground/Shield |
| Impulse durability (line-line) (General) | B2 - 1 kV / 25 A |
| Near-end crosstalk attenuation (General) | ≥ 35 dB (250 MHz/100 Ω/link) |
| Number of positions (Ambient conditions) | 8 |
| Surge protection fault message (General) | none |
| Impulse durability (line-earth) (General) | B2 - 4 kV/100 A |
| Residual voltage at In(line-line) (General) | ≤ 15 V |
| Ambient temperature (operation) (Dimensions) | -40 °C ... 70 °C |
| Operating effective current ICat UC (General) | ≤ 1 µA |
| Voltage protection level Up(line-line) (General) | ≤ 9 V (B2 - 1 kV / 25 A) |
| Voltage protection level Up(line-earth) (General) | ≤ 900 V (B2 - 4 kV / 100 A) |
| Maximum continuous voltage UC(wire-wire) (General) | ≤ 3.3 V DC (± 60 V DC/PoE+) |
| Total discharge current Itotal(8/20) µs (General) | 10 kA |
| Ambient temperature (storage/transport) (Dimensions) | -40 °C ... 70 °C |
| Nominal discharge current In(8/20) µs (line-line) (General) | 100 A |
| Nominal pulse current Ian (10/700) µs (line-line) (General) | ≤ 40 A |
| Standards/specifications (Connection, equipotential bonding) | IEC 61643-21 2002 |
| Nominal discharge current In(8/20) µs (line-earth) (General) | 2 kA (per signal pair) |
| Nominal pulse current Ian (10/700) µs (line-earth) (General) | ≤ 160 A |
| Output voltage limitation at 1 kV/µs (line-line) spike (General) | ≤ 85 V (PoE) |
| Output voltage limitation at 1 kV/µs (line-earth) spike (General) | ≤ 700 V |
| Output voltage limitation at 1 kV/µs (line-line) static (General) | ≤ 9 V |
| Output voltage limitation at 1 kV/µs (line-earth) static (General) | ≤ 700 V |
Technical specifications and performance data
Installation and operation guide