| Parameter | Value |
|---|---|
| GTIN | 4046356048989 |
| Orderkey | 2880642 |
| (General) | C3 - 2 kV/25 A |
| Catalog page | Page 155 (C-4-2017) |
| Packing unit | 1 pc |
| Country of origin | DE (Germany) |
| Custom tariff number | 85363010 |
| (Ambient conditions) | DIN VDE 0110-1 |
| Rated current (General) | 250 mA (25 °C) |
| Type (Ambient conditions) | Connecting plug |
| Color (Ambient conditions) | silver |
| Depth (Key Commercial Data) | 16.6 mm |
| Width (Key Commercial Data) | 44.5 mm |
| (Standards and Regulations) | For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |
| Height (Key Commercial Data) | 58 mm |
| Residual current IPE (General) | ≤ 100 µA |
| Inductivity in series (General) | 0.11 µH |
| VDE requirement class (General) | C1 |
| Degree of protection (Dimensions) | IP40 |
| IEC test classification (General) | C1 |
| Screw thread (Protective circuit) | M2 |
| Mounting type (Ambient conditions) | Direct assembly on the device interface |
| Connection method (Connection data) | PVC Litz wire, 1.0 mm², 0.5 m length |
| (Connection, equipotential bonding) | DIN EN 61643-21 |
| Weight per Piece (excluding packing) | 53.300 g |
| Housing material (Ambient conditions) | ABS, metal-plated |
| Response time tA(line-line) (General) | ≤ 500 ns |
| Stripping length (Protective circuit) | 5 mm |
| China RoHS (Standards and Regulations) | Environmentally Friendly Use Period = 50 |
| Connection method (Protective circuit) | Screw connection & D-SUB-9 |
| Response time tA(line-earth) (General) | ≤ 500 ns |
| Tightening torque (Protective circuit) | 0.25 Nm |
| Maximum continuous voltage UC (General) | 5.2 V DC |
| Degree of pollution (Ambient conditions) | 2 |
| Direction of action (Ambient conditions) | Line-Line & Line-Earth Ground |
| Impulse durability (line-line) (General) | C1 - 500 V / 250 A |
| Number of positions (Ambient conditions) | 4 |
| Surge protection fault message (General) | none |
| Connection method IN (Protective circuit) | Screw terminal blocks |
| Impulse durability (line-earth) (General) | C1 - 500 V / 250 A |
| Overvoltage category (Ambient conditions) | II |
| Connection method OUT (Protective circuit) | D-SUB-9 connector |
| Connection technology (Protective circuit) | 2-wire (shielded) |
| Residual voltage at In(line-line) (General) | ≤ 25 V |
| Ambient temperature (operation) (Dimensions) | -20 °C ... 75 °C |
| Residual voltage at In(line-earth) (General) | ≤ 25 V |
| Operating effective current ICat UC (General) | ≤ 100 µA |
| Conductor cross section AWG (Protective circuit) | 26 ... 16 |
| Voltage protection level Up(line-line) (General) | ≤ 25 V (C1 - 500 V / 250 A) |
| Voltage protection level Up(line-earth) (General) | ≤ 25 V (C1 - 500 V / 250 A) |
| Conductor cross section solid (Protective circuit) | 0.14 mm² ... 1.5 mm² |
| Total discharge current Itotal(8/20) µs (General) | 350 A |
| Ambient temperature (storage/transport) (Dimensions) | -20 °C ... 75 °C |
| Conductor cross section flexible (Protective circuit) | 0.14 mm² ... 1.5 mm² |
| Standards/regulations (Connection, equipotential bonding) | IEC 61643-21 |
| Nominal discharge current In(8/20) µs (line-line) (General) | 350 A |
| Output voltage limitation (10/700) µs (line-line) (General) | ≤ 15 V (Uo=4 kV) |
| Standards/specifications (Connection, equipotential bonding) | IEC 61643-21 |
| Cut-off frequency fg (3 dB), sym. in 100 Ohm system (General) | typ. 70 MHz |
| Nominal discharge current In(8/20) µs (line-earth) (General) | 350 A |
| Output voltage limitation (10/700) µs (line-earth) (General) | ≤ 15 V (Uo=4 kV) |
| Output voltage limitation at 1 kV/µs (line-line) spike (General) | ≤ 20 V |
| Output voltage limitation at 1 kV/µs (line-earth) spike (General) | ≤ 20 V |
| Output voltage limitation at 1 kV/µs (line-line) static (General) | ≤ 14 V |
| Max. discharge current Imax(8/20) µs maximum (line-line) (General) | 350 A |
| Output voltage limitation at 1 kV/µs (line-earth) static (General) | ≤ 14 V |
| Standards for cearances and creepage distances (Ambient conditions) | IEC 60664-1 |
| Max. discharge current Imax(8/20) µs maximum (line-earth) (General) | 350 A |
Technical specifications and performance data