| Parameter | Value |
|---|---|
| GTIN | 4017918161927 |
| Note | Made to Order (non-returnable) |
| Orderkey | 2818795 |
| (General) | |
| Catalog page | Page 122 (TT-2005) |
| Packing unit | 1 pc |
| Country of origin | DE (Germany) |
| (Connection data) | E VDE 0845-3-1 |
| Custom tariff number | 85363010 |
| Type (Ambient conditions) | Attachment plug |
| Color (Ambient conditions) | black |
| Depth (Key Commercial Data) | 102 mm |
| Width (Key Commercial Data) | 25.4 mm |
| (Standards and Regulations) | No hazardous substances above threshold values |
| Height (Key Commercial Data) | 25.4 mm |
| Nominal current IN (General) | 150 mA |
| Residual current IPE (General) | ≤ 1 µA |
| Resistance in series (General) | 1 Ω |
| Inductivity in series (General) | 39 µH ±10 % |
| VDE requirement class (General) | C2 |
| Degree of protection (Dimensions) | IP20 |
| IEC test classification (General) | C2 |
| Mounting type (Ambient conditions) | Connection-specific intermediate plugging |
| Input attenuation aE, sym. (General) | |
| Weight per Piece (excluding packing) | 109.000 g |
| Housing material (Ambient conditions) | Aluminum |
| Input attenuation aE, asym. (General) | |
| Response time tA(line-line) (General) | ≤ 10 ns |
| China RoHS (Standards and Regulations) | Environmentally friendly use period: unlimited = EFUP-e |
| Connection method (Protective circuit) | RJ45 |
| REACh SVHC (Standards and Regulations) | Lead 7439-92-1 |
| Response time tA(line-earth) (General) | ≤ 100 ns |
| Maximum continuous voltage UC (General) | 185 V DC |
| Standards/regulations (Connection data) | Draft IEC 64644-1 |
| Direction of action (Ambient conditions) | Line-Line & Line-Earth Ground |
| Surge protection fault message (General) | none |
| Connection method IN (Protective circuit) | RJ45 socket |
| Connection method OUT (Protective circuit) | RJ45 socket |
| Residual voltage at In(line-line) (General) | ≤ 50 V |
| Ambient temperature (operation) (Dimensions) | -25 °C ... 85 °C |
| Residual voltage at In(line-earth) (General) | ≤ 150 V |
| Operating effective current ICat UC (General) | ≤ 10 µA |
| Short-circuit current self-quenching (General) | 150 mA |
| Voltage protection level Up(line-line) (General) | ≤ 300 V |
| Voltage protection level Up(line-earth) (General) | ≤ 1.4 kV |
| Nominal discharge current In(8/20) µs (line-earth) (General) | 2.5 kA |
| Output voltage limitation at 1 kV/µs (line-line) spike (General) | ≤ 300 V |
| Output voltage limitation at 1 kV/µs (line-earth) spike (General) | ≤ 1.4 kV |
| Output voltage limitation at 1 kV/µs (line-line) static (General) | ≤ 300 V |
| Output voltage limitation at 1 kV/µs (line-earth) static (General) | ≤ 1.4 kV |
| Max. discharge current Imax(8/20) µs maximum (line-earth) (General) |
Technical specifications and performance data