Technical Specifications

ParameterValue
GTIN4017918819576
Orderkey2838542
(General)D1 - 1 kA
Catalog pagePage 119 (C-4-2017)
Packing unit10 pc
Country of originDE (Germany)
Custom tariff number85363010
Altitude (Dimensions)≤ 2000 m (amsl (above mean sea level))
Rated current (General)380 mA AC (25 °C)
Type (Ambient conditions)LSA-PLUS module
Color (Ambient conditions)jet black RAL 9005
Depth (Key Commercial Data)52.4 mm
Width (Key Commercial Data)9.4 mm
(Standards and Regulations)No hazardous substances above threshold values
Height (Key Commercial Data)21 mm
Nominal voltage UN (General)60 V DC
Residual current IPE (General)≤ 2 µA
Resistance in series (General)3.3 Ω 20 %
Capacity (line-earth) (General)typ. 1 nF
Degree of protection (Dimensions)IP20
IEC test classification (General)B2
Mounting type (Ambient conditions)On CT-TERMIBLOCK and LSA-PLUS disconnect strip
Connection method (Connection data)Spring contact
(Connection, equipotential bonding)EN 61643-21 2001 + A1:2009 + A2:2013
Weight per Piece (excluding packing)10.580 g
Housing material (Ambient conditions)PA 6.6
Input attenuation aE, asym. (General)typ. 0.3 dB (≤ 500 kHz / 100 Ω)
China RoHS (Standards and Regulations)Environmentally friendly use period: unlimited = EFUP-e
Connection method (Protective circuit)can be plugged into COMTRAB-TERMIBLOCK and LSA-PLUS disconnect and switching strips
Response time tA(line-earth) (General)≤ 1 ns
Maximum continuous voltage UC (General)60 V DC
Degree of pollution (Ambient conditions)2
Direction of action (Ambient conditions)Line-Line & Line-Earth Ground
Surge protection fault message (General)none
Connection method IN (Protective circuit)COMTRAB plug-in system
Impulse durability (line-earth) (General)B2 - 4 kV/100 A
Overvoltage category (Ambient conditions)II
Connection method OUT (Protective circuit)COMTRAB plug-in system
Connection technology (Protective circuit)LSA-PLUS
Ambient temperature (operation) (Dimensions)-25 °C ... 75 °C
Residual voltage at In(line-earth) (General)≤ 95 V
Operating effective current ICat UC (General)≤ 70 µA
Voltage protection level Up(line-earth) (General)≤ 240 V (C2 - 10 kV / 5 kA)
Total discharge current Itotal(8/20) µs (General)10 kA
Total discharge current Itotal(10/350) µs (General)2.5 kA
Voltage protection level Upstatic (line-earth) (General)≤ 85 V (C2 - 10 kV / 5 kA)
Flammability rating according to UL 94 (Ambient conditions)V-0
Alternating current carrying capacity (line-earth) (General)5 A - 1 s
Standards/specifications (Connection, equipotential bonding)IEC 61643-21 2000 + corrigendum 2001 + A1:2008, modified + A2:2012
Nominal discharge current In(8/20) µs (line-earth) (General)5 kA
Nominal pulse current Ian (10/1000) µs (line-earth) (General)100 A
Residual voltage with Ian (10/1000) µs (line-earth) (General)≤ 16 V
Pulse discharge current Iimp(10/350) µs (line-earth) (General)1 kA
Output voltage limitation at 1 kV/µs (line-earth) spike (General)≤ 160 V
Cut-off frequency fg (3 dB), asym. (PE) in 100 Ohm system (General)typ. 2 MHz
Output voltage limitation at 1 kV/µs (line-earth) static (General)≤ 160 V
Arrester can be tested with CHECKMASTER from software version: (Ambient conditions)From SW rev. 1.10

Product Description

LSA-PLUS plug-in protection protection circuit for 2 conductors of signal circuits with unilateral ground. Rated voltage: 60 V DC
Key Features
  • Industrial grade quality
  • RoHS compliant
  • CE certified
  • 1-year warranty

Product Documents

Datasheet

Technical specifications and performance data

User Manual

Installation and operation guide

Top