| Parameter | Value |
|---|---|
| GTIN | 4017918819569 |
| Orderkey | 2838539 |
| (General) | D1 - 1 kA |
| Catalog page | Page 166 (C-4-2017) |
| Packing unit | 10 pc |
| Country of origin | DE (Germany) |
| Custom tariff number | 85363010 |
| Altitude (Dimensions) | ≤ 2000 m (amsl (above mean sea level)) |
| Rated current (General) | 380 mA AC (25 °C) |
| Type (Ambient conditions) | LSA-PLUS module |
| Color (Ambient conditions) | jet black RAL 9005 |
| Depth (Key Commercial Data) | 52.4 mm |
| Width (Key Commercial Data) | 9.4 mm |
| (Standards and Regulations) | No hazardous substances above threshold values |
| Height (Key Commercial Data) | 21 mm |
| Nominal voltage UN (General) | 110 V AC |
| Capacity (line-line) (General) | typ. 100 pF |
| Residual current IPE (General) | ≤ 2 µA (per path) |
| Resistance in series (General) | 3.3 Ω 20 % |
| Degree of protection (Dimensions) | IP20 |
| IEC test classification (General) | B2 |
| Mounting type (Ambient conditions) | On CT-TERMIBLOCK and LSA-PLUS disconnect strip |
| Connection method (Connection data) | Spring contact |
| (Connection, equipotential bonding) | EN 61643-21 2001 + A1:2009 + A2:2013 |
| Input attenuation aE, sym. (General) | typ. 0.3 dB (≤ 1.8 MHz/100 Ω) |
| Max. required back-up fuse (General) | 150 mA (T/IEC 60127-2/3) |
| Weight per Piece (excluding packing) | 9.900 g |
| Housing material (Ambient conditions) | PA 6.6 |
| Response time tA(line-line) (General) | ≤ 1 ns |
| China RoHS (Standards and Regulations) | Environmentally friendly use period: unlimited = EFUP-e |
| Connection method (Protective circuit) | can be plugged into COMTRAB-TERMIBLOCK and LSA-PLUS disconnect and switching strips |
| Response time tA(line-earth) (General) | ≤ 100 ns |
| Maximum continuous voltage UC (General) | 60 V DC |
| Transmission speed (Ambient conditions) | 42 Mbps |
| Degree of pollution (Ambient conditions) | 2 |
| Direction of action (Ambient conditions) | Line-Line & Line-Earth Ground |
| Impulse durability (line-line) (General) | B2 - 4 kV/100 A |
| Surge protection fault message (General) | none |
| Connection method IN (Protective circuit) | COMTRAB plug-in system |
| Impulse durability (line-earth) (General) | B2 - 4 kV/100 A |
| Overvoltage category (Ambient conditions) | II |
| Connection method OUT (Protective circuit) | COMTRAB plug-in system |
| Connection technology (Protective circuit) | LSA-PLUS |
| Residual voltage at In(line-line) (General) | ≤ 10 V |
| Ambient temperature (operation) (Dimensions) | -25 °C ... 75 °C |
| Residual voltage at In(line-earth) (General) | ≤ 55 V |
| Operating effective current ICat UC (General) | ≤ 5 µA (in the signal circuit) |
| Voltage protection level Up(line-line) (General) | ≤ 260 V (C2 - 10 kV / 5 kA) |
| Voltage protection level Up(line-earth) (General) | ≤ 800 V (C2 - 10 kV / 5 kA) |
| Total discharge current Itotal(8/20) µs (General) | 10 kA |
| Total discharge current Itotal(10/350) µs (General) | 2.5 kA |
| Voltage protection level Upstatic (line-line) (General) | ≤ 10 V (C2 - 10 kV / 5 kA) |
| Voltage protection level Upstatic (line-earth) (General) | ≤ 60 V (C2 - 10 kV / 5 kA) |
| Flammability rating according to UL 94 (Ambient conditions) | V-0 |
| Alternating current carrying capacity (line-earth) (General) | 5 A - 1 s |
| Nominal discharge current In(8/20) µs (line-line) (General) | 5 kA |
| Standards/specifications (Connection, equipotential bonding) | IEC 61643-21 2000 + corrigendum 2001 + A1:2008, modified + A2:2012 |
| Cut-off frequency fg (3 dB), sym. in 100 Ohm system (General) | typ. 20 MHz |
| Nominal discharge current In(8/20) µs (line-earth) (General) | 5 kA |
| Nominal pulse current Ian (10/1000) µs (line-line) (General) | 100 A |
| Residual voltage with Ian (10/1000) µs (line-line) (General) | ≤ 10 V |
| Nominal pulse current Ian (10/1000) µs (line-earth) (General) | 100 A |
| Residual voltage with Ian (10/1000) µs (line-earth) (General) | ≤ 12 V |
| Pulse discharge current Iimp(10/350) µs (line-earth) (General) | 1 kA |
| Output voltage limitation at 1 kV/µs (line-line) spike (General) | ≤ 260 V |
| Output voltage limitation at 1 kV/µs (line-earth) spike (General) | ≤ 800 V |
| Arrester can be tested with CHECKMASTER from software version: (Ambient conditions) | From SW rev. 1.10 |