| Parameter | Value |
|---|---|
| GTIN | 4017918104757 |
| Note | Made to Order (non-returnable) |
| Orderkey | 2807968 |
| (General) | D1 - 2.5 kA |
| Catalog page | Page 107 (C-6-2013) |
| Packing unit | 1 pc |
| Country of origin | DE (Germany) |
| Custom tariff number | 85363010 |
| (Ambient conditions) | IEC 60664-1 |
| Rated current (General) | 200 mA (25 °C) |
| Type (Ambient conditions) | LSA-PLUS module |
| Color (Ambient conditions) | black |
| Depth (Key Commercial Data) | 68.5 mm |
| Width (Key Commercial Data) | 111 mm |
| Height (Key Commercial Data) | 22 mm |
| Nominal voltage UN (General) | 24 V DC |
| Capacity (line-line) (General) | 1.1 nF (f=1 MHz / VR= 0 V) |
| Residual current IPE (General) | ≤ 1 µA (per path) |
| Resistance in series (General) | 10 Ω ±10 % |
| Capacity (line-earth) (General) | 1 pF (typ.) |
| Degree of protection (Dimensions) | IP20 |
| IEC test classification (General) | C1 |
| Mounting type (Ambient conditions) | On CT-TERMIBLOCK and LSA-PLUS disconnect strip |
| Input attenuation aE, sym. (General) | 1.5 dB (Typ. up to 2 MHz / 50 Ω) |
| Max. required back-up fuse (General) | 200 mA |
| Weight per Piece (excluding packing) | 127.000 g |
| Housing material (Ambient conditions) | PBT |
| Input attenuation aE, asym. (General) | |
| Response time tA(line-line) (General) | ≤ 1 ns |
| Connection method (Protective circuit) | can be plugged into COMTRAB-TERMIBLOCK and LSA-PLUS disconnect and switching strips |
| Response time tA(line-earth) (General) | ≤ 100 ns |
| Maximum continuous voltage UC (General) | 40 V DC |
| Standards/regulations (Connection data) | IEC 61643-21 |
| Direction of action (Ambient conditions) | Line-Line & Line-Earth Ground |
| Impulse durability (line-line) (General) | C1 - 1 kV/500 A |
| Surge protection fault message (General) | none |
| Connection method IN (Protective circuit) | COMTRAB plug-in system |
| Impulse durability (line-earth) (General) | C1 - 1 kV/500 A |
| Connection method OUT (Protective circuit) | COMTRAB plug-in system |
| Standards/specifications (Connection data) | IEC 61643-21 2000 |
| Residual voltage at In(line-line) (General) | ≤ 55 V |
| Ambient temperature (operation) (Dimensions) | -25 °C ... 75 °C |
| Operating effective current ICat UC (General) | ≤ 5 µA (a-b) |
| Total discharge current Itotal(8/20) µs (General) | 10 kA |
| Flammability rating according to UL 94 (Ambient conditions) | V0 |
| Cut-off frequency fg (3 dB), sym. in 50 Ohm system (General) | 7 MHz (typ.) |
| Nominal discharge current In(8/20) µs (line-line) (General) | 5 kA |
| Cut-off frequency fg (3 dB), sym. in 150 Ohm system (General) | 4 MHz (typ.) |
| Cut-off frequency fg (3 dB), sym. in 600 Ohm system (General) | 900 kHz (typ.) |
| Nominal discharge current In(8/20) µs (line-earth) (General) | 5 kA |
| Output voltage limitation at 1 kV/µs (line-line) spike (General) | ≤ 95 V |
| Output voltage limitation at 1 kV/µs (line-earth) spike (General) | ≤ 650 V |
| Output voltage limitation at 1 kV/µs (line-line) static (General) | ≤ 60 V |
| Max. discharge current Imax(8/20) µs maximum (line-line) (General) | 5 kA |
| Output voltage limitation at 1 kV/µs (line-earth) static (General) | ≤ 650 V |
| Standards for cearances and creepage distances (Ambient conditions) | VDE 0110-1 |
| Max. discharge current Imax(8/20) µs maximum (line-earth) (General) | 5 kA |
| Arrester can be tested with CHECKMASTER from software version: (Ambient conditions) | From SW rev. 1.00 |
Technical specifications and performance data
Installation and operation guide