| Parameter | Value |
|---|---|
| GTIN | 4046356181822 |
| Note | Made to Order (non-returnable) |
| Orderkey | 2920829 |
| (General) | D1 - 2.5 kA |
| Catalog page | Page 168 (C-4-2017) |
| Packing unit | 10 pc |
| Country of origin | DE (Germany) |
| Custom tariff number | 85363010 |
| (Ambient conditions) | IEC 60664-1 |
| Altitude (Dimensions) | ≤ 2000 mm (amsl (above mean sea level)) |
| Rated current (General) | 1.5 A AC (per path) |
| Type (Ambient conditions) | LSA-PLUS module |
| Color (Ambient conditions) | gray |
| Depth (Key Commercial Data) | 41.35 mm |
| Width (Key Commercial Data) | 113.3 mm |
| Height (Key Commercial Data) | 22.5 mm |
| Nominal voltage UN (General) | 110 V AC |
| Residual current IPE (General) | ≤ 20 µA |
| Resistance in series (General) | ≤ 10 mΩ |
| Capacity (line-earth) (General) | typ. 5 pF |
| Degree of protection (Dimensions) | IP20 |
| IEC test classification (General) | C2 |
| Mounting type (Ambient conditions) | On CT-TERMIBLOCK and LSA-PLUS disconnect strip |
| Connection method (Connection data) | Spring contact |
| (Connection, equipotential bonding) | EN 61643-21 2001 + A1:2009 + A2:2013 |
| Weight per Piece (excluding packing) | 75.000 g |
| Housing material (Ambient conditions) | PBT |
| Connection method (Protective circuit) | can be plugged into COMTRAB-TERMIBLOCK and LSA-PLUS disconnect and switching strips |
| Response time tA(line-earth) (General) | ≤ 100 ns |
| Maximum continuous voltage UC (General) | 60 V DC |
| Direction of action (Ambient conditions) | Line-Line & Line-Earth Ground |
| Number of positions (Ambient conditions) | 20 |
| Surge protection fault message (General) | none |
| Connection method IN (Protective circuit) | COMTRAB plug-in system |
| Impulse durability (line-earth) (General) | C2 - 10 kV/5 kA |
| Connection method OUT (Protective circuit) | COMTRAB plug-in system |
| Connection technology (Protective circuit) | LSA-PLUS |
| Ambient temperature (operation) (Dimensions) | -25 °C ... 75 °C |
| Operating effective current ICat UC (General) | ≤ 1 µA (per path) |
| Flammability rating according to UL 94 (Ambient conditions) | V-0 |
| Alternating current carrying capacity (line-earth) (General) | 10 A - 1 s |
| Standards/specifications (Connection, equipotential bonding) | IEC 61643-21 2000 + corrigendum 2001 + A1:2008, modified + A2:2012 |
| Nominal discharge current In(8/20) µs (line-earth) (General) | 5 kA |
| Nominal pulse current Ian (10/1000) µs (line-earth) (General) | 100 A |
| Pulse discharge current Iimp(10/350) µs (line-earth) (General) | 2.5 kA |
| Output voltage limitation at 1 kV/µs (line-earth) spike (General) | ≤ 500 V |
| Standards for cearances and creepage distances (Ambient conditions) | VDE 0110-1 |
Technical specifications and performance data
Installation and operation guide