| Parameter | Value |
|---|---|
| GTIN | 4017918075408 |
| Note | Made to Order (non-returnable) |
| Orderkey | 2807926 |
| (General) | D1 - 2.5 kA |
| Catalog page | Page 107 (C-6-2013) |
| Packing unit | 1 pc |
| Country of origin | DE (Germany) |
| (Connection data) | EN 61643-21 2001 + A1:2009 + A2:2013 |
| Custom tariff number | 85363010 |
| Altitude (Dimensions) | ≤ 2000 mm (amsl (above mean sea level)) |
| Rated current (General) | 1.5 A AC (75 °C) |
| Type (Ambient conditions) | LSA-PLUS module |
| Color (Ambient conditions) | jet black RAL 9005 |
| Depth (Key Commercial Data) | 68.5 mm |
| Width (Key Commercial Data) | 111 mm |
| (Standards and Regulations) | No hazardous substances above threshold values |
| Height (Key Commercial Data) | 22 mm |
| Nominal voltage UN (General) | 24 V DC |
| Residual current IPE (General) | ≤ 1 µA (19x) |
| Degree of protection (Dimensions) | IP20 |
| IEC test classification (General) | C1 |
| Mounting type (Ambient conditions) | On CT-TERMIBLOCK and LSA-PLUS disconnect strip |
| Weight per Piece (excluding packing) | 106.510 g |
| Housing material (Ambient conditions) | PBT |
| Input attenuation aE, asym. (General) | typ. 0.1 dB (≤ 2 MHz / 50 Ω) |
| Capacity (line-signalground) (General) | typ. 1.1 nF (1 MHz) |
| China RoHS (Standards and Regulations) | Environmentally friendly use period: unlimited = EFUP-e |
| Connection method (Protective circuit) | can be plugged into COMTRAB-TERMIBLOCK and LSA-PLUS disconnect and switching strips |
| Response time tA(line-earth) (General) | ≤ 100 ns |
| Maximum continuous voltage UC (General) | 40 V DC |
| Direction of action (Ambient conditions) | Line-Signal Ground/Shield & Signal Ground/Shield-Earth Ground |
| Surge protection fault message (General) | none |
| Connection method IN (Protective circuit) | COMTRAB plug-in system |
| Impulse durability (line-earth) (General) | C2 - 10 kV/5 kA |
| Connection method OUT (Protective circuit) | COMTRAB plug-in system |
| Standards/specifications (Connection data) | IEC 61643-21 2000 + corrigendum 2001 + A1:2008, modified + A2:2012 |
| Ambient temperature (operation) (Dimensions) | -25 °C ... 75 °C |
| Residual voltage at In(line-earth) (General) | ≤ 30 V |
| Operating effective current ICat UC (General) | ≤ 5 µA (18x) |
| Response time tA (line-signalground) (General) | ≤ 1 ns |
| Impulse durability (line-signalground) (General) | C3 - 23 A |
| Impulse durability (signalground-earth) (General) | D1 - 2.5 kA |
| Total discharge current Itotal(8/20) µs (General) | 10 kA |
| Residual voltage at In(line-signalground) (General) | ≤ 85 V |
| Flammability rating according to UL 94 (Ambient conditions) | V-0 |
| Nominal discharge current In(8/20) µs (line-line) (General) | 119 A (per path) |
| Nominal discharge current In(8/20) µs (line-earth) (General) | 5 kA (per path) |
| Pulse discharge current Iimp(10/350) µs (line-earth) (General) | 2.5 kA |
| Output voltage limitation at 1 kV/µs (line-earth) spike (General) | ≤ 650 V |
| Cut-off frequency fg (3 dB), asym. (GND) in 50 Ohm system (General) | typ. 10 MHz |
| Max. discharge current Imax(8/20) µs maximum (line-line) (General) | 119 A (per path) |
| Standards for cearances and creepage distances (Ambient conditions) | VDE 0110-1 |
| Cut-off frequency fg (3 dB), asym. (GND) in 150 Ohm system (General) | typ. 2.5 MHz |
| Cut-off frequency fg (3 dB), asym. (GND) in 600 Ohm system (General) | typ. 650 kHz |
| Max. discharge current Imax(8/20) µs maximum (line-earth) (General) | 5 kA (per path) |
| Nominal discharge current In(8/20) µs (signalground-earth) (General) | 5 kA (per path) |
| Nominal pulse current Ian (10/1000) µs (line-signalground) (General) | 23 A |
| Residual voltage with Ian (10/1000) µs (line-signalground) (General) | ≤ 65 V |
| Pulse discharge current Iimp(10/350) µs (signalground-earth) (General) | 2.5 kA |
| Output voltage limitation at 1 kV/µs (line-signalground) spike (General) | ≤ 70 V |
| Output voltage limitation at 1 kV/µs (line-signalground) static (General) | ≤ 60 V |
| Arrester can be tested with CHECKMASTER from software version: (Ambient conditions) | From SW rev. 1.00 |
Technical specifications and performance data