| Parameter | Value |
|---|---|
| GTIN | 4046356293211 |
| Orderkey | 2803166 |
| Catalog page | Page 176 (C-4-2017) |
| Packing unit | 1 pc |
| Note (General) | To meet the discharge conditions for DC voltages, please note the following information: "The surge protective device should be used together with a transmitter unit, which shuts down in the event of a short-circuit." |
| Country of origin | US (United States) |
| Custom tariff number | 85363010 |
| (Ambient conditions) | IEC 60664-1 |
| Type (Ambient conditions) | Attachment plug |
| (Additional descriptions) | D1 - 1 kA |
| Color (Ambient conditions) | nickel |
| Depth (Key Commercial Data) | 47 mm |
| Width (Key Commercial Data) | 24 mm |
| Height (Key Commercial Data) | 24 mm |
| Degree of protection (Dimensions) | IP68 |
| Mounting type (Ambient conditions) | Connection-specific intermediate plugging |
| Weight per Piece (excluding packing) | 75.000 g |
| Housing material (Ambient conditions) | Brass (CuZn) |
| Connection method (Protective circuit) | N connector 50 Ω |
| Rated current (Additional descriptions) | 10 A |
| Standards/regulations (Connection data) | IEC 61643-21 |
| Direction of action (Ambient conditions) | Line-Shield/Earth Ground |
| Connection method IN (Protective circuit) | N connector, female |
| Frequency range (Additional descriptions) | 0 Hz ... 6 GHz |
| Connection method OUT (Protective circuit) | N connector, female |
| Standards/specifications (Connection data) | IEC 61643-21 2000 |
| Ambient temperature (operation) (Dimensions) | -40 °C ... 90 °C |
| Capacity (line-earth) (Additional descriptions) | typ. 1.5 pF |
| VDE requirement class (Additional descriptions) | C2 |
| IEC test classification (Additional descriptions) | C2 |
| Input attenuation aE, asym. (Additional descriptions) | 0.1 dB (≤ 6 GHz) |
| Response time tA(line-earth) (Additional descriptions) | ≤ 100 ns |
| Maximum continuous voltage UC (Additional descriptions) | 70 V DC |
| Capacity asymmetrical (shield) (Additional descriptions) | typ. 1.5 pF |
| Response time tA (line-shield) (Additional descriptions) | ≤ 100 ns |
| Surge protection fault message (Additional descriptions) | none |
| Impulse durability (line-earth) (Additional descriptions) | C2 - 10 kV/5 kA |
| Impulse durability (line-shield) (Additional descriptions) | C2 - 10 kV/5 kA |
| Operating effective current ICat UC (Additional descriptions) | ≤ 1 µA |
| Nominal discharge current In(8/20) µs (Additional descriptions) | 5 kA |
| Voltage protection level Up(line-earth) (Additional descriptions) | ≤ 800 V (C2 - 4 kV / 2 kA) |
| Total discharge current Itotal(8/20) µs (Additional descriptions) | 5 kA |
| Voltage protection level Up(line-shield) (Additional descriptions) | ≤ 800 V (C2 - 4 kV / 2 kA) |
| Maximum continuous voltage UC(line-earth) (Additional descriptions) | 70 V DC |
| Standards for cearances and creepage distances (Ambient conditions) | DIN VDE 0110-1 |
| Standing wave ratio SWR in a 50 Ω system (Additional descriptions) | typ. 1.15 (≤ 6 GHz) |
| Alternating current carrying capacity (line-shield) (Additional descriptions) | 5 A - 1 s |
| Nominal discharge current In(8/20) µs (line-earth) (Additional descriptions) | 5 kA |
| Nominal discharge current In(8/20) µs (line-shield) (Additional descriptions) | 5 kA |
| Nominal pulse current Ian (10/1000) µs (Core-Shield) (Additional descriptions) | 100 A |
| Permissible HF power Pmaxat VSWR = xx (50 ohm system) (Additional descriptions) | 30 W (VSWR = 1.15) |
| Impulse discharge current (10/350) µs, peak value limp (Additional descriptions) | 1 kA |
| Output voltage limitation at 1 kV/µs (line-earth) spike (Additional descriptions) | ≤ 650 V |
| Output voltage limitation at 1 kV/µs (line-earth) static (Additional descriptions) | ≤ 650 V |
| Output voltage limitation at 1 kV/µs (line-shield) spike (Additional descriptions) | ≤ 650 V |
| Max. discharge current Imax(8/20) µs maximum (line-earth) (Additional descriptions) | 10 kA |
| Output voltage limitation at 1 kV/µs (line-shield) static (Additional descriptions) | ≤ 650 V |
| Max. discharge current Imax(8/20) µs maximum (line-shield) (Additional descriptions) | 10 kA |
| Cut-off frequency fg (3 dB), asym. (shield) in 50 Ohm system (Additional descriptions) | > 6 GHz |
Technical specifications and performance data
Installation and operation guide