| Parameter | Value |
|---|---|
| GTIN | 4046356678247 |
| Orderkey | 2801056 |
| (General) | D1 - 2.5 kA |
| Catalog page | Page 178 (C-4-2017) |
| Packing unit | 1 pc |
| Country of origin | CN (China) |
| (Connection data) | EN 61643-21/A1 2009 |
| Custom tariff number | 85363010 |
| Altitude (Dimensions) | 2000 m |
| Frequency range (General) | 0.8 GHz ... 2.25 GHz |
| Type (Ambient conditions) | Attachment plug |
| Color (Ambient conditions) | nickel |
| Width (Key Commercial Data) | 25 mm |
| Height (Key Commercial Data) | 77.5 mm |
| Length (Key Commercial Data) | 81.5 mm |
| Nominal current IN (General) | 5 A (25 °C) |
| VDE requirement class (General) | C2 |
| Degree of protection (Dimensions) | IP68 |
| IEC test classification (General) | C2 |
| Mounting type (Ambient conditions) | Connection-specific intermediate plugging |
| Weight per Piece (excluding packing) | 260.000 g |
| Housing material (Ambient conditions) | HPb59-1 |
| Input attenuation aE, asym. (General) | ≤ 0.2 dB (50 Ω) |
| Connection method (Protective circuit) | N connector 50 Ω |
| Direction of action (Ambient conditions) | Line-Shield/Earth Ground |
| Number of positions (Ambient conditions) | 1 |
| Surge protection fault message (General) | none |
| Total surge current (8/20) µs (General) | 60 kA |
| Connection method IN (Protective circuit) | N connector, male |
| Impulse durability (line-earth) (General) | C1 - 1 kV/500 A |
| Connection method OUT (Protective circuit) | N connector, female |
| Standards/specifications (Connection data) | IEC 61643-21/A1 2008 |
| Total surge current (10/350) µs (General) | 20 kA |
| Ambient temperature (operation) (Dimensions) | -40 °C ... 85 °C |
| Voltage protection level Up(line-earth) (General) | ≤ 15 V (6 kV / 3 kA) |
| Voltage protection level Up(line-shield) (General) | ≤ 25 V (C2 - 10 kV / 5 kA) |
| Standing wave ratio SWR in a 50 Ω system (General) | typ. 1.2 |
| Nominal discharge current In(8/20) µs (line-earth) (General) | 50 kA |
| Nominal discharge current In(8/20) µs (line-shield) (General) | 50 kA |
| Permissible HF power Pmaxat VSWR = xx (50 ohm system) (General) | ≤ 500 W |
| Impulse discharge current (10/350) µs, peak value limp (General) | ≤ 20 kA |
| Output voltage limitation at 1 kV/µs (line-earth) spike (General) | ≤ 1 V |
| Output voltage limitation at 1 kV/µs (line-earth) static (General) | ≤ 1 V |
| Output voltage limitation at 1 kV/µs (line-shield) spike (General) | ≤ 1 V |
| Standards for cearances and creepage distances (Ambient conditions) | IEC 60664-1 |
| Max. discharge current Imax(8/20) µs maximum (line-earth) (General) | 60 kA |
| Max. discharge current Imax(8/20) µs maximum (line-shield) (General) | 60 kA |
Technical specifications and performance data