| Parameter | Value |
|---|---|
| C3 | |
| Type | Attachment plug |
| Color | nickel |
| Depth | 77.5 mm |
| Width | 25 mm |
| Height | 78.7 mm |
| Length | 77.5 mm |
| Mounting type | Connection-specific intermediate plugging |
| Frequency range | 0.8 GHz ... 2.25 GHz |
| Housing material | HPb59-1 |
| Connection method | N connector 50 Ω |
| Connection type IN | N connector, female |
| Nominal current IN | 5 A (25 °C) |
| Connection type OUT | N connector, female |
| Direction of action | Line-Shield/Earth Ground |
| Number of positions | 1 |
| Degree of protection | IP68 |
| IEC test classification | C2 |
| Input attenuation aE, asym. | typ. 0.1 dB |
| Total surge current (8/20) µs | 60 kA |
| Ambient temperature (operation) | -40 °C ... 85 °C |
| Total surge current (10/350) µs | 20 kA |
| Impulse durability (conductor-ground) | C1 - 1 kV/500 A |
| Max. discharge current Imax(8/20) µs | 60 kA |
| Nominal discharge current In(8/20) µs | 50 kA |
| Voltage protection level Up(core-ground) | ≤ 25 V (C2 - 10 kV / 5 kA) |
| Voltage protection level Up(core-shield) | ≤ 5 V (C1 - 1 kV/500 A) |
| Standing wave ratio SWR in a 50 Ω system | typ. 1.2 |
| Standards for cearances and creepage distances | IEC 60664-1 |
| Nominal discharge current In(8/20) µs (Core-Earth) | 50 kA |
| Nominal discharge current In(8/20) µs (Core-Shield) | 50 kA |
| Permissible HF power Pmaxat VSWR = xx (50 ohm system) | ≤ 500 W |
| Impulse discharge current (10/350)˽µs, peak value limp | 20 kA |
| Output voltage limitation at 1 kV/µs (Core-Earth) spike | ≤ 1 V |
| Output voltage limitation at 1 kV/µs (Core-Shield) spike | ≤ 1 V |
| Max. discharge current Imax(8/20) µs maximum (Core-Earth) | 60 kA |
| Max. discharge current Imax(8/20) µs maximum (Core-Shield) | 60 kA |
Technical specifications and performance data