| Parameter | Value |
|---|---|
| 50 V DC (UL 1077) | |
| Fuse | F1 (fast blow) |
| Type | Male |
| Color | gray (RAL 7042) |
| Depth | 52 mm |
| Width | 12.3 mm |
| Height | 45 mm |
| General | When mounted in rows, the nominal device current can be limited to just 80% or must be overdimensioned accordingly. |
| Fuse type | Automatic device |
| Product type | Thermomagnetic device circuit breakers |
| Voltage drop | 0.29 V (at 1 x In) |
| Humidity test | 240 h, 95 % RH, 40 °C |
| Mounting type | on base element |
| Rated voltage | 50 V DC (IEC 60934) |
| Identification | UL Listed UL 508 |
| Product family | CB TM |
| Tripping level | Trip-free mechanism (positive) |
| No. of channels | 1 |
| Open side panel | No |
| Switch-on delay | typ. 2 ms |
| Tripping method | TM (thermomagnetic) |
| Article revision | 06 |
| Rated current IN | 6 A (IEC 60934) |
| Auxiliary circuit | 277 V AC / 0.5 A (Low-induction) |
| Connection method | pluggable |
| Device resistance | 50 mΩ |
| Power dissipation | 1.8 W (in nominal operation per channel) |
| Shock (operation) | 15g (IEC 60068-2-27, Test Ea) |
| Type of actuation | S type |
| Degree of pollution | 2 |
| Dielectric strength | 3000 V AC (Actuation area) |
| Dimensional drawing | |
| Number of positions | 1 |
| Rated surge voltage | 2.5 kV (Increased insulation in actuation area) |
| Degree of protection | IP30 (Actuation area) |
| Required backup fuse | 24 A (I > Icn) |
| Complete module depth | 77.3 mm |
| Complete module width | 12.3 mm |
| Vibration (operation) | 5g (IEC 60068-2-6, Test Fc) |
| Complete module height | 90 mm |
| Switching cycles, max. | 6000 (at 1 x In) |
| Standards/specifications | EN 60934 |
| Insulating material group | II |
| Insulation resistance Riso | > 100 MΩ (500 V DC) |
| Max. operating current Imax | 1 A |
| Rated insulation voltage Ui | 277 V AC (UL 1077) |
| Minimum operating current Imin | 10 mA |
| Ambient temperature (operation) | -30 °C ... 60 °C |
| Maximum operating voltage UmaxDC | 240 V |
| Minimum operating voltage UminDC | 10 V |
| Short-circuit switching capacity | 1000 A AC (277 V AC) |
| Maximum operating voltage Umax.AC | 240 V |
| Flammability rating according to UL 94 | V-0 |
| Ambient temperature (storage/transport) | -40 °C ... 80 °C |
| Rated short-circuit switching capacity Icn | 600 A (50 V DC) |
Technical specifications and performance data
Installation and operation guide