| Parameter | Value |
|---|---|
| 18 V DC ... 30 V DC | |
| Fuse | electronic |
| Note | Interference emission |
| Type | Male |
| Color | gray (RAL 7042) |
| Depth | 52 mm |
| Width | 12.3 mm |
| Height | 45 mm |
| General | When mounted in rows without convection cooling, the nominal device current should only be led to a maximum of 80% due to the thermal effect during continuous operation (100% operating factor).Special precautionary measures must be taken in systems or machines, to prevent components from restarting (e.g., use of a safety PLC).Parallel connection of multiple circuit breakers is not permitted. |
| Voltage | < 3 V DC (Low state) |
| Product type | Device circuit breakers |
| Pulse length | min. 20 ms |
| Voltage drop | 100 mV (at IN) |
| Humidity test | 96 h, 95 % RH, 40 °C |
| Mounting type | on base element |
| Shutdown time | 200 ms (see time/current characteristic curve) |
| Identification | UL Listed UL 508 |
| Output current | max. 0.2 A (Short-circuit-proof) |
| Output voltage | 24 V DC |
| Product family | CB E |
| No. of channels | 1 |
| Switch-on delay | typ. 2 ms |
| Tripping method | E (electronic) |
| Article revision | 03 |
| Connection method | pluggable |
| Fail-safe element | 6 A DC |
| Operating voltage | 24 V DC |
| Power dissipation | 0.66 W (Nominal operation) |
| Nominal current IN | 4 A |
| Current consumption | typ. 2.6 mA (at 24 V DC) |
| Degree of pollution | 2 |
| Dielectric strength | max. 30 V DC (Load circuit) |
| Dimensional drawing | |
| Input voltage range | 7 V DC ... 30 V DC (Reset with falling edge) |
| Number of positions | 1 |
| Rated surge voltage | 0.5 kV |
| Degree of protection | IP30 (Actuation area) |
| Max. capacitive load | 20000 µF |
| Required backup fuse | not required, integrated failsafe element |
| Standard designation | EMV |
| Temperature derating | 4 A (at 50 °C) |
| Complete module depth | 77.3 mm |
| Complete module width | 12.3 mm |
| Vibration (operation) | 3g (according to IEC 60068-2-6, Test Fc) |
| Complete module height | 90 mm |
| Contact connection type | Positive-switching signal output |
| Undervoltage switch-off | < 14 V (typ. OFF) |
| Standards/specifications | EN 61000-6-3 |
| Active current limitation | typ. 1.25 x IN |
| Closed circuit current I0 | typ. 8 mA (When switched on) |
| MTBF (IEC 61709, SN 29500) | 8320000 h (at 25 °C with 80 % load) |
| Ambient temperature (operation) | -25 °C ... 50 °C (non-condensing) |
| Flammability rating according to UL 94 | V-0 |
| Ambient temperature (storage/transport) | -40 °C ... 70 °C |