Key Specifications
GTIN:4046356048941
Orderkey:2880561
(General):D1 - 5 kA
Catalog page:Page 180 (C-4-2017)
Supplier Information
Products: 0
Usually ships within 2-3 business days
Quality Guaranteed
Fast Shipping
Technical Support

Technical Specifications

ParameterValue
GTIN4046356048941
Orderkey2880561
(General)D1 - 5 kA
Catalog pagePage 180 (C-4-2017)
Packing unit1 pc
Country of originDE (Germany)
Custom tariff number85363010
(Ambient conditions)DIN VDE 0110-1
Altitude (Dimensions)≤ 4000 m (amsl (above mean sea level))
Rated current (General)400 mA
Frequency range (General)47 MHz ... 2.5 GHz
Type (Ambient conditions)Housing for surface mounting
Color (Ambient conditions)silver
Depth (Key Commercial Data)71.5 mm
Width (Key Commercial Data)144.9 mm
Height (Key Commercial Data)31.5 mm
Nominal voltage UN (General)14 V DC (vertical)
Residual current IPE (General)≤ 2 µA (per channel)
Resistance in series (General)3.3 Ω ±20 %
Inductivity in series (General)typ. 5 µH (f = 10 kHz)
Degree of protection (Dimensions)IP40
IEC test classification (General)B2
Mounting type (Ambient conditions)Screw mounting
Connection method (Connection data)Screw connection
(Connection, equipotential bonding)EN 50083-2 CLASS-A
Weight per Piece (excluding packing)228.240 g
Housing material (Ambient conditions)Zinc die-cast
Input attenuation aE, asym. (General)≤ 1 dB (5 MHz ... 2,2 GHz / 75 Ω)
Connection method (Protective circuit)F connector
Maximum continuous voltage UC (General)20 V DC
Degree of pollution (Ambient conditions)2
Direction of action (Ambient conditions)Line-Shield/Earth Ground
Near-end crosstalk attenuation (General)≥ 40 dB (5 MHz ... 2,4 GHz / 75 Ω)
Number of positions (Ambient conditions)5
Response time tA (line-shield) (General)≤ 1 ns
Surge protection fault message (General)none
Connection method IN (Protective circuit)F connector, female
Overvoltage category (Ambient conditions)II
Connection method OUT (Protective circuit)F connector, female
Impulse durability (line-shield) (General)B2 - 4 kV/100 A
Impulse durability (shield-earth) (General)C2 - 10 kA
Ambient temperature (operation) (Dimensions)-25 °C ... 55 °C
Operating effective current ICat UC (General)≤ 2 µA (per channel)
Total discharge current Itotal(8/20) µs (General)10 kA
Voltage protection level Up(line-shield) (General)≤ 500 V (C2 - 4 kV / 2 kA)
Ambient temperature (storage/transport) (Dimensions)-40 °C ... 80 °C
Standards/specifications (Connection, equipotential bonding)IEC 61643-21 2000 + A1:2008 + A2:2012
Nominal discharge current In(8/20) µs (line-shield) (General)2.5 kA
Nominal pulse current Ian (10/700) µs (Core-Shield) (General)100 A
Nominal pulse current Ian (10/1000) µs (Core-Shield) (General)100 A
Standards for cearances and creepage distances (Ambient conditions)IEC 60664-1
Output voltage limitation at 1 kV/µs (line-shield) static (General)≤ 80 V
Max. discharge current Imax(8/20) µs maximum (line-shield) (General)2.5 kA
Cut-off frequency fg (3 dB), asym. (shield) in 75 Ohm system (General)> 2.5 GHz

Product Description

Surge protection for antenna splitters in satellite installations. IN and OUT via F connectors, 5 channels for signals from satellite installations and terrestrial antennas, grounding on the outside o
Key Features
  • Industrial grade quality
  • RoHS compliant
  • CE certified
  • 1-year warranty

Product Documents

Datasheet

Technical specifications and performance data

User Manual

Installation and operation guide

Top