| Parameter | Value |
|---|---|
| GTIN | 4046356620437 |
| Note | Made to Order (non-returnable) |
| Orderkey | 2800625 |
| (General) | 1455 V AC (200 ms / safe failure mode) |
| Catalog page | Page 73 (C-4-2017) |
| Packing unit | 1 pc |
| Country of origin | DE (Germany) |
| (Connection data) | EN 61643-11 2012 |
| Custom tariff number | 85363030 |
| (Ambient conditions) | N-PE |
| Altitude (Dimensions) | ≤ 2000 m (amsl (above mean sea level)) |
| Type (Ambient conditions) | Installation module |
| Color (Ambient conditions) | jet black RAL 9005 |
| Depth (Key Commercial Data) | 27.4 mm |
| Width (Key Commercial Data) | 22.5 mm |
| EN type (Ambient conditions) | T3 |
| Height (Key Commercial Data) | 43 mm |
| Nominal voltage UN (General) | 230/400 V AC (TN-S) |
| Combination wave UOC (General) | 6 kV |
| Nominal frequency fN (General) | 50 Hz (60 Hz) |
| Residual current IPE (General) | ≤ 3 µA |
| Rated load current IL (General) | 16 A (30 °C) |
| Response time tA(L-N) (General) | ≤ 25 ns |
| Response time tA(L-PE) (General) | ≤ 100 ns |
| Degree of protection (Dimensions) | IP20 |
| TOV behavior at UT(L-N) (General) | 335 V AC (5 s / withstand mode) |
| Mounting type (Ambient conditions) | Screw mounting |
| TOV behavior at UT(L-PE) (General) | 440 V AC (5 s / withstand mode) |
| TOV behavior at UT(N-PE) (General) | 1200 V AC (200 ms / safe failure mode) |
| Max. required back-up fuse (General) | 16 A (MCB B) |
| Number of ports (Ambient conditions) | One |
| Weight per Piece (excluding packing) | 42.400 g |
| Housing material (Ambient conditions) | PA 6.6 |
| Reference test voltage UREF (General) | 255 V AC |
| Stripping length (Protective circuit) | 10 mm |
| Connection method (Protective circuit) | Spring-cage connection |
| Standby power consumption PC (General) | ≤ 400 mVA |
| Energy absorption symmetrical (General) | 200 J (L-N (L)) |
| Mode of protection (Ambient conditions) | L-N |
| Degree of pollution (Ambient conditions) | 2 |
| Enery absorption, asymmetrical (General) | 230 J (L(N)-PE) |
| Number of positions (Ambient conditions) | 2 |
| Standards/specifications (Connection data) | IEC 61643-11 2011 |
| Voltage protection level Up(L-N) (General) | ≤ 1.3 kV |
| Voltage protection level Up(L-PE) (General) | ≤ 1.5 kV |
| Voltage protection level Up(N-PE) (General) | ≤ 1.5 kV |
| Ambient temperature (operation) (Dimensions) | -30 °C ... 75 °C |
| IEC power supply system (Ambient conditions) | TN-S |
| Short-circuit current rating ISCCR (General) | 1 kA AC |
| Max. backup fuse with branch wiring (General) | 16 A (MCB B) |
| Permissible humidity (operation) (Dimensions) | 5 % ... 95 % |
| Max. discharge current Imax(8/20) µs (General) | 8 kA |
| Conductor cross section AWG (Protective circuit) | 24 ... 14 |
| Maximum backup fuse for through wiring (General) | 16 A (MCB B) |
| Nominal discharge current In(8/20) µs (General) | 3 kA |
| Conductor cross section solid (Protective circuit) | 0.2 mm² ... 2.5 mm² |
| Surge protection fault message (Ambient conditions) | optical |
| Ambient temperature (storage/transport) (Dimensions) | -30 °C ... 75 °C |
| Conductor cross section flexible (Protective circuit) | 0.2 mm² ... 2.5 mm² |
| Maximum continuous operating voltage UC(L-N) (General) | 275 V AC |
| Maximum continuous operating voltage UC(L-PE) (General) | 440 V AC |
| Maximum continuous operating voltage UC(N-PE) (General) | 440 V AC |
| Flammability rating according to UL 94 (Ambient conditions) | V-0 |
| Distance between live and grounded parts (Ambient conditions) | 3 mm |
Technical specifications and performance data
Installation and operation guide