| Parameter | Value |
|---|---|
| GTIN | 4055626793344 |
| Orderkey | 1078433 |
| (General) | 440 V AC (120 min / safe failure mode) |
| (Drawings) | |
| Catalog page | Page 76 (C-4-2019) |
| Packing unit | 1 |
| Depth (Drawings) | 34 mm |
| Width (Drawings) | 36.5 mm |
| ETIM 5.0 (eCl@ss) | EC000941 |
| ETIM 6.0 (eCl@ss) | EC000941 |
| ETIM 7.0 (eCl@ss) | EC000941 |
| Height (Drawings) | 56 mm |
| (Connection data) | EN 61643-11 2012 |
| Custom tariff number | 85354000 |
| (Ambient conditions) | N-PE |
| Altitude (Dimensions) | ≤ 2000 m (amsl (above mean sea level)) |
| Color (Ambient conditions) | light grey RAL 7035 |
| EN type (Ambient conditions) | T2 / T3 |
| Nominal voltage UN (General) | 100 V AC ... 230 V AC (TN-S) |
| eCl@ss 8.0 (Classifications) | 27130805 |
| eCl@ss 9.0 (Classifications) | 27130805 |
| Dimensional drawing (Drawings) | |
| Nominal frequency fN (General) | 50 Hz (60 Hz) |
| Residual current IPE (General) | ≤ 5 µA |
| Shock (operation) (Dimensions) | 25g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z) |
| Rated load current IL (General) | 16 A |
| Response time tA(L-N) (General) | ≤ 25 ns |
| Response time tA(L-PE) (General) | ≤ 100 ns |
| Response time tA(N-PE) (General) | ≤ 100 ns |
| Degree of protection (Dimensions) | IP20 |
| Screw thread (Protective circuit) | M3 |
| TOV behavior at UT(L-N) (General) | 336 V AC (5 s / withstand mode) |
| Accessibility (Ambient conditions) | Accessible |
| Mounting type (Ambient conditions) | 4 mm screw |
| TOV behavior at UT(L-PE) (General) | 440 V AC (5 s / withstand mode) |
| TOV behavior at UT(N-PE) (General) | 1200 V AC (200 ms / safe failure mode) |
| Vibration (operation) (Dimensions) | 5g (5 ... 500 Hz / 2.5 h / X, Y, Z) |
| Combination wave UOC(L-N) (General) | 10 kV |
| Combination wave UOC(L-PE) (General) | 10 kV |
| Combination wave UOC(N-PE) (General) | 20 kV |
| Housing material (Ambient conditions) | PA 6.6 |
| Protection class (Ambient conditions) | I |
| Stripping length (Protective circuit) | 8 mm |
| Connection method (Protective circuit) | Screw terminal blocks |
| REACh SVHC (Standards and Regulations) | Lead 7439-92-1 |
| Tightening torque (Protective circuit) | 0.6 Nm |
| Mode of protection (Ambient conditions) | L-N |
| Standards/regulations (Connection data) | IEC 61643-11 2011 |
| Degree of pollution (Ambient conditions) | 2 |
| SPD failure behavior (Ambient conditions) | OCM |
| Voltage protection level Up(L-N) (General) | ≤ 1.3 kV |
| Voltage protection level Up(L-PE) (General) | ≤ 1.5 kV |
| Voltage protection level Up(N-PE) (General) | ≤ 1.5 kV |
| Ambient temperature (operation) (Dimensions) | -40 °C ... 80 °C |
| IEC power supply system (Ambient conditions) | TN-S |
| IEC test classification (Ambient conditions) | II / III |
| Short-circuit current rating ISCCR (General) | 10 kA (6 A gG backup fuse) |
| Max. backup fuse with branch wiring (General) | 16 A (MCB B/C) |
| Maximum continuous voltage UC(N-PE) (General) | 265 V AC |
| Permissible humidity (operation) (Dimensions) | 5 % ... 95 % |
| Conductor cross section solid (Protective circuit) | 0.2 mm² ... 4 mm² |
| Follow current interrupt rating Ifi(N-PE) (General) | 100 A () |
| Total discharge current Itotal(8/20) µs (General) | 20 kA |
| Ambient temperature (storage/transport) (Dimensions) | -40 °C ... 80 °C |
| Conductor cross section flexible (Protective circuit) | 0.2 mm² ... 2.5 mm² |
| Max. backup fuse with V-type through wiring (General) | 16 A (MCB B/C) |
| Maximum continuous operating voltage UC(L-N) (General) | 305 V AC |
| Nominal discharge current In(8/20) µs (L-N) (General) | 5 kA |
| Maximum continuous operating voltage UC(L-PE) (General) | 265 V AC |
| Nominal discharge current In(8/20) µs (L-PE) (General) | 5 kA |
| Nominal discharge current In(8/20) µs (N-PE) (General) | 10 kA |
| Maximum discharge current Imax(8/20) µs (L-N) (General) | 10 kA |
| Maximum discharge current Imax(8/20) µs (L-PE) (General) | 10 kA |
| Maximum discharge current Imax(8/20) µs (N-PE) (General) | 20 kA |
| Flammability rating according to UL 94 (Ambient conditions) | V-0 |
| Distance between live and grounded parts (Ambient conditions) | 3 mm |
| Installation location of the disconnect device (Ambient conditions) | Internal |
| 2 conductors with same cross section, solid max. (Protective circuit) | 1.5 mm² |
| 2 conductors with same cross section, solid min. (Protective circuit) | 0.2 mm² |
| 2 conductors with same cross section, stranded max. (Protective circuit) | 1.5 mm² |
| 2 conductors with same cross section, stranded min. (Protective circuit) | 0.2 mm² |
Technical specifications and performance data
Installation and operation guide