| Parameter | Value |
|---|---|
| • The installation notes/Design In documents online on the download page at phoenixcontact.com/products must be observed for this product. | |
| Note | WEEE/RoHS-compliant, free of whiskers according to IEC 60068-2-82/JEDEC JESD 201 |
| Pitch | 10 mm |
| Width [w] | 10 mm |
| Height [h] | 31.5 mm |
| Length [l] | 30.2 mm |
| Application | Internal part molded |
| Height [h3] | 31.5 mm |
| Length [l1] | 15.5 mm |
| Length [l2] | 10.4 mm |
| Safety note | • WARNING: Only electrically qualified personnel may install and operate the product. They must observe the following safety notes. The qualified personnel must be familiar with the basics of electrical engineering. They must be able to recognize and prevent danger. The relevant symbol on the packaging indicates that only personnel familiar with electrical engineering are allowed to install and operate the product. |
| Product type | Panel feed-through terminal block |
| Product family | VDFK 6 |
| Color (Housing) | black (9005) |
| Article revision | 02 |
| Connector system | VDFK 6 |
| Contact material | Cu alloy |
| Stripping length | 9 mm |
| Connection method | Screw connection with tension sleeve |
| Tightening torque | 1.5 Nm ... 1.8 Nm |
| Type of packaging | packed in cardboard |
| Nominal current IN | 41 A |
| Nominal voltage UN | 500 V |
| Dimensional drawing | |
| Insulating material | PA |
| Number of positions | 1 |
| Nominal cross section | 6 mm² |
| Rated voltage (III/3) | 500 V |
| Surface characteristics | tin-plated |
| Insulating material group | I |
| Internal cylindrical gage | A5 |
| CTI according to IEC 60112 | 600 |
| Rated surge voltage (III/3) | 6 kV |
| Conductor cross section rigid | 0.2 mm² ... 10 mm² |
| Conductor cross section flexible | 0.2 mm² ... 6 mm² |
| Rated insulation voltage (III/3) | 500 V |
| minimum creepage distance (III/3) | 6.3 mm |
| Flammability rating according to UL 94 | V0 |
| Comparative tracking index (IEC 60112) | CTI 600 |
| 2 conductors with same cross section, solid | 0.2 mm² ... 4 mm² |
| 2 conductors with same cross section, flexible | 0.2 mm² ... 4 mm² |
| minimum clearance value - non-homogenous field (III/3) | 5.5 mm |
| Connection direction of the conductor to plug-in direction | 0 ° |
| Glow wire flammability index GWFI according to EN 60695-2-12 | 850 |
| Glow wire ignition temperature GWIT according to EN 60695-2-13 | 775 |
| Temperature for the ball pressure test according to EN 60695-10-2 | 125 °C |
| Conductor cross section, flexible, with ferrule, with plastic sleeve | 0.25 mm² ... 6 mm² |
| Conductor cross section flexible, with ferrule without plastic sleeve | 0.25 mm² ... 6 mm² |
| 2 conductors with same cross section, flexible, with ferrule without plastic sleeve | 0.25 mm² ... 2.5 mm² |
| 2 conductors with the same cross section, flexible, with TWIN ferrule with plastic sleeve | 0.5 mm² ... 4 mm² |
Technical specifications and performance data