| Parameter | Value |
|---|---|
| GTIN | 4046356299039 |
| Orderkey | 3245066 |
| Catalog page | Page 255 (C-1-2017) |
| Packing unit | 50 pc |
| Width (General) | 15 mm |
| Height (General) | 49.8 mm |
| Length (General) | 55 mm |
| Country of origin | GR (Greece) |
| Note (Dimensions) | Terminal point |
| Custom tariff number | 85369010 |
| Height NS 32 (General) | 56 mm |
| Screw thread (Dimensions) | M6 |
| Height NS 35/7,5 (General) | 51 mm |
| Note (Key Commercial Data) | Assembly instructions:For secure fastening of the neutral busbar, supports must be set at the beginning and end of each terminal strip as well as every 20 cm on longer terminal strips. |
| Color (Key Commercial Data) | blue |
| (Standards and Regulations) | No hazardous substances above threshold values |
| Stripping length (Dimensions) | 16 mm |
| Connection method (Dimensions) | Special and hybrid connection |
| Potentials (Key Commercial Data) | 1 |
| Tightening torque max (Dimensions) | 3.7 Nm |
| Tightening torque, min (Dimensions) | 3.2 Nm |
| Weight per Piece (excluding packing) | 46.930 g |
| Open side panel (Key Commercial Data) | No |
| China RoHS (Standards and Regulations) | Environmentally friendly use period: unlimited = EFUP-e |
| Number of levels (Key Commercial Data) | 1 |
| Nominal current IN (Key Commercial Data) | 110 A |
| Nominal voltage UN (Key Commercial Data) | 400 V |
| Degree of pollution (Key Commercial Data) | 3 |
| Insulating material (Key Commercial Data) | PA |
| Rated surge voltage (Key Commercial Data) | 6 kV |
| Maximum load current (Key Commercial Data) | 110 A (with 35 mm² conductor cross section) |
| Overvoltage category (Key Commercial Data) | III |
| Nominal cross section (Key Commercial Data) | 35 mm² |
| Number of connections (Key Commercial Data) | 2 |
| Conductor cross section AWG max. (Dimensions) | 2 |
| Conductor cross section AWG min. (Dimensions) | 18 |
| Connection in acc. with standard (Dimensions) | IEC 60947-7-1 |
| Conductor cross section solid max. (Dimensions) | 35 mm² |
| Conductor cross section solid min. (Dimensions) | 0.75 mm² |
| Insulating material group (Key Commercial Data) | I |
| Conductor cross section flexible max. (Dimensions) | 35 mm² |
| Conductor cross section flexible min. (Dimensions) | 0.75 mm² |
| Connection in acc. with standard (Connection data) | IEC 60947-7-1 |
| Max. AWG conductor cross section, flexible (Dimensions) | 2 |
| Min. AWG conductor cross section, flexible (Dimensions) | 18 |
| Flammability rating according to UL 94 (Connection data) | V2 |
| Flammability rating according to UL 94 (Key Commercial Data) | V2 |
| 2 conductors with same cross section, solid max. (Dimensions) | 10 mm² |
| 2 conductors with same cross section, solid min. (Dimensions) | 0.75 mm² |
| 2 conductors with same cross section, stranded max. (Dimensions) | 10 mm² |
| 2 conductors with same cross section, stranded min. (Dimensions) | 0.75 mm² |
| Maximum power dissipation for nominal condition (Key Commercial Data) | 4.06 W |
| Conductor cross section flexible, with ferrule with plastic sleeve max. (Dimensions) | 35 mm² |
| Conductor cross section flexible, with ferrule with plastic sleeve min. (Dimensions) | 0.75 mm² |
| Conductor cross section flexible, with ferrule without plastic sleeve max. (Dimensions) | 35 mm² |
| Conductor cross section flexible, with ferrule without plastic sleeve min. (Dimensions) | 0.75 mm² |
| 2 conductors with same cross section, stranded, ferrules without plastic sleeve, max. (Dimensions) | 10 mm² |
| 2 conductors with same cross section, stranded, ferrules without plastic sleeve, min. (Dimensions) | 0.75 mm² |
| 2 conductors with same cross section, stranded, TWIN ferrules with plastic sleeve, max. (Dimensions) | 6 mm² |
| 2 conductors with same cross section, stranded, TWIN ferrules with plastic sleeve, min. (Dimensions) | 0.75 mm² |
Technical specifications and performance data