| Parameter | Value |
|---|---|
| max. 1.6 W (With interconnected arrangement of several fuse terminal blocks in the event of overload) | |
| Fuse | G / 5 x 20 |
| Note | Please observe the current carrying capacity of the DIN rails. |
| Color | black (RAL 9005) |
| Width | 6.2 mm |
| Height | 70.8 mm |
| output | (Permanent) |
| General | The current is determined by the fuse used, the voltage by the selected LED.If the fuse is faulty, the downstream circuit will not be disconnected. |
| Fuse type | Glass / ceramics / ... |
| Product type | Ground terminal block |
| Screw thread | M3 |
| Torque range | 0.6 Nm ... 0.8 Nm |
| Mounting type | NS 35/7,5 |
| Rated current | 6.3 A (4 mm²) |
| Rated voltage | 250 V |
| Grounding foot | Yes |
| Identification | II 3 G Ex ec llC Gc |
| Number of rows | 1 |
| Nominal current | 6.3 A |
| Nominal voltage | 24 V |
| Open side panel | No |
| Article revision | 10 |
| Stripping length | 9 mm |
| Cross section AWG | 26 ... 10 (converted acc. to IEC) |
| LED current range | 0.31 mA ... 0.95 mA |
| LED voltage range | 12 V AC/DC ... 30 V AC/DC |
| Tightening torque | 0.6 ... 0.8 Nm |
| Contact resistance | 5 mΩ |
| Depth on NS 35/15 | 80.5 mm |
| Degree of pollution | 3 |
| Depth on NS 35/7,5 | 73 mm |
| Insulating material | PA |
| Rated surge voltage | 4 kV |
| Maximum load current | 6.3 A (the current is determined by the fuse used) |
| Overvoltage category | III |
| Nominal cross section | 4 mm² |
| Number of connections | 2 |
| Connection capacity AWG | 26 ... 10 |
| Rated cross section AWG | 12 |
| Ex-certified accessories | 1205053 SZS 0,6X3,5 |
| Connection capacity rigid | 0.14 mm² ... 6 mm² |
| Insulating material group | I |
| Internal cylindrical gage | A4 |
| Maximum power dissipation | max. 1.6 W (with single arrangement of the fuse terminal block in the event of overload) |
| Operating temperature range | -60 °C ... 130 °C |
| Connection capacity flexible | 0.14 mm² ... 6 mm² |
| Conductor cross section rigid | 0.14 mm² ... 6 mm² |
| Ambient temperature (assembly) | -5 °C ... 70 °C |
| Ambient temperature (actuation) | -5 °C ... 70 °C |
| Ambient temperature (operation) | -60 °C ... 110 °C (Operating temperature range incl. self-heating; for max. short-term operating temperature, see RTI Elec.) |
| Number of connections per level | 2 |
| Conductor cross section flexible | 0.5 mm² ... 6 mm² |
| Connection in acc. with standard | IEC 60947-7-2/IEC 60947-7-3 |
| Permissible humidity (operation) | 20 % ... 90 % |
| Flammability rating according to UL 94 | V0 |
| Smoke gas toxicity NFPA 130 (SMP 800C) | passed |
| Ambient temperature (storage/transport) | -25 °C ... 60 °C (for a short time, not exceeding 24 h, -60 °C to +70 °C) |
| Conductor cross section, flexible [AWG] | 20 ... 10 (converted acc. to IEC) |
| Permissible humidity (storage/transport) | 30 % ... 70 % |
| Surface flammability NFPA 130 (ASTM E 162) | passed |
| 2 conductors with same cross section, solid | 0.14 mm² ... 1.5 mm² |
| 2 conductors with same cross section, stranded | 0.14 mm² ... 1.5 mm² |
| Static insulating material application in cold | -60 °C |
| Maximum power dissipation for nominal condition | 1.02 W |
| Calorimetric heat release NFPA 130 (ASTM E 1354) | 28 MJ/kg |
| 2 conductors with the same cross-section AWG rigid | 26 ... 16 |
| 2 conductors with the same cross-section AWG flexible | 26 ... 16 |
| Fire protection for rail vehicles (DIN EN 45545-2) R22 | HL 1 - HL 3 |
| Fire protection for rail vehicles (DIN EN 45545-2) R23 | HL 1 - HL 3 |
| Fire protection for rail vehicles (DIN EN 45545-2) R24 | HL 1 - HL 3 |
| Fire protection for rail vehicles (DIN EN 45545-2) R26 | HL 1 - HL 3 |
| Specific optical density of smoke NFPA 130 (ASTM E 662) | passed |
| Flexible conductor cross section (ferrule with plastic sleeve) | 0.14 mm² ... 4 mm² |
| Relative insulation material temperature index (Elec., UL 746 B) | 130 °C |
| Conductor cross-section flexible (ferrule without plastic sleeve) | 0.14 mm² ... 4 mm² |
| Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21)) | 130 °C |
| Conductor cross section flexible, with ferrule without plastic sleeve max. | 4 mm² |
| Conductor cross section flexible, with ferrule without plastic sleeve min. | 0.14 mm² |
| Single conductor/terminal point, flexible, with ferrule, without plastic sleeve, AWG | 26 ... 12 |
Technical specifications and performance data
Installation and operation guide