| Parameter | Value |
|---|---|
| GTIN | 4046356707701 |
| Orderkey | 2320416 |
| (General) | 15 Hz ... 150 Hz, 2.3g, 90 min. |
| Catalog page | Page 288 (C-4-2017) |
| Packing unit | 1 pc |
| Shock (General) | 18 ms, 30g, in each space direction (according to IEC 60068-2-27) |
| Country of origin | US (United States) |
| Custom tariff number | 85072080 |
| (Ambient conditions) | 10 min. (40 A) |
| Disposal (Output data) | Used batteries must not be thrown away with household waste, they should instead be disposed of in accordance with applicable national regulations. They can also be returned to Phoenix Contact or the manufacturer. |
| UL approvals (General) | UL/C-UL listed UL 508 |
| Net weight (Output data) | 10.8 kg |
| Output fuse (Input data) | 2x 25 A ATOF 32V |
| Depth (Key Commercial Data) | 178 mm |
| IQ technology (Output data) | Yes |
| Memory medium (Output data) | Pure lead AGM |
| Width (Key Commercial Data) | 172 mm |
| Height (Key Commercial Data) | 177 mm |
| Protection class (Output data) | III |
| Mounting position (Output data) | horizontally, on a mounting plate |
| Shipbuilding approval (General) | DNV GL (EMC A), ABS |
| Vibration (operation) (General) | |
| Degree of pollution (Dimensions) | 2 |
| Output current Imax (Input data) | 45 A |
| Connection in series (Input data) | No |
| Degree of protection (Dimensions) | IP20 |
| Buffer period (Ambient conditions) | 50 min. (10 A) |
| Degree of protection (Output data) | IP20 |
| Nominal output voltage (Input data) | 24 V DC |
| Weight per Piece (excluding packing) | 10,000.000 g |
| Standard - Electrical safety (General) | EN 60950-1/VDE 0805 (SELV) |
| Connection in acc. with standard (General) | CUL |
| Nominal input voltage (Ambient conditions) | 24 V DC |
| Ambient temperature (operation) (Dimensions) | -25 °C ... 60 °C |
| Ambient temperature (storage/transport) (Dimensions) | -40 °C ... 60 °C |
| Max. permissible relative humidity (operation) (Dimensions) | ≤ 95 % |
| Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations (General) | EN 50178/VDE 0160 (PELV) |
Technical specifications and performance data